Distillation Reflux Ratio Calculator

Model column overhead section choose a target reflux ratio estimate flows and duties see energy impact and convert between reflux and distillate rates built for process engineers students and operators with shareable results and unit aware inputs includes supports simple total condenser assumptions with latent heat entry provides helpful warnings on unrealistic values cases

Inputs

Results

Enter inputs and press Calculate to see results.

What Is Distillation Reflux?

Distillation reflux is the portion of condensed overhead vapor that is returned to the column as liquid. The returning liquid flows down the rectifying section and contacts rising vapor, enriching the top with the more volatile component. Reflux ratio R is defined as L over D, where L is external reflux and D is distillate rate. When R increases, the operating line on a McCabe–Thiele diagram moves closer to the diagonal. That reduces the number of theoretical stages required for a given separation, but increases condenser duty and internal circulation. When R decreases toward the minimum reflux, separation becomes difficult and the required stages approach infinity. Practical design balances column height and energy use, typically choosing a ratio between 1.2 and 1.5 times the minimum value. In operation, reflux is adjusted to control overhead composition, recover from disturbances, or meet product specifications. A total condenser simplifies top balances, since V equals L plus D and R equals L divided by D. With partial condensers, definitions follow the external reflux stream. Because real columns deviate from ideal behavior, measurements should use consistent units and validated flowmeters, and calculations should state assumptions about latent heat, phase behavior, and side draws if present.

FAQs

It is the ratio of external reflux L returned to the column to distillate D withdrawn at the top. It governs top section internal flows and separation difficulty.
Increase reflux to tighten overhead purity, recover after disturbances, or reduce the effective number of stages required. Expect higher condenser duty and energy use.
Yes. Enter a latent heat per flow unit. The tool multiplies by overhead flow to report approximate condenser and reboiler duties under constant molar overflow.
Use any consistent set. For example kmol/h with kJ per kmol or kg/h with kJ per kg. The results reflect the label you enter for clarity.
If you provide V and D, L equals V minus D for a total condenser. A negative value means V is less than D, which is physically inconsistent.
No. Minimum reflux requires composition data and an equilibrium model. This tool focuses on operational balances. Use a design package for Underwood and Gilliland steps.
Yes. After calculating, click Download CSV to save the key results. You can also print the page for your records.

Related Calculators


Mole-Mass Converter Calculator
Percent Composition Calculator
Molality from Mass Calculator
Equilibrium Constant Calculator
Graham's Law Diffusion Calculator

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.