Ambient Temperature Derating Calculator

Enter base ampacity, insulation rating, and ambient temperature for accurate derating calculations. See correction factor, reduced capacity, and compliance notes instantly on screen below.

Calculator Inputs

Tip: Base ampacity is commonly tabulated at 30°C ambient. If your reference differs, this tool normalizes using the same rating table for a consistent correction.

Ampacity at the reference ambient temperature.
Common reference is 30°C.
Local maximum expected temperature.
Select the conductor insulation rating.
Optional: reduces allowable ampacity further.
Rounding affects displayed reduction percent.
Reset

Example Data Table

These examples illustrate typical reductions as ambient temperature rises.

Base Ampacity (A) Reference (°C) Ambient (°C) Rating (°C) Effective Factor Derated Ampacity (A)
100 30 40 90 0.9100 91
150 30 45 75 0.8200 123
80 30 50 90 0.8200 66
200 30 35 60 0.9100 182

Formula Used

The calculator applies an ambient temperature correction factor based on the insulation rating.

Step 1: Get the factor at the reference temperature, F_ref, for the selected rating.

Step 2: Get the factor at the actual ambient temperature, F_amb, for the same rating.

Step 3: Compute the effective correction factor:

F_eff = F_amb / F_ref

Step 4: Compute the derated ampacity:

A_derated = A_base × F_eff

Optional safety margin: If a margin M% is used:

A_final = A_derated × (1 − M/100)

Reduction percent:

Reduction% = (1 − A_final / A_base) × 100

Correction factors are applied in 5°C bands for practical planning.

How to Use This Calculator

  1. Enter the base ampacity from your conductor table or datasheet.
  2. Confirm the reference ambient used by that base value (often 30°C).
  3. Enter the highest expected ambient temperature for the installation.
  4. Select the conductor insulation temperature rating (60°C, 75°C, or 90°C).
  5. Optionally add a safety margin for conservative planning.
  6. Press Calculate Derating to view results above the form.
  7. Use the CSV or PDF buttons to export your latest calculation.

If your ambient falls outside the supported table, the tool will block the calculation and prompt you to verify your inputs.

Technical Article

1) Why ambient derating matters

Conductor ampacity tables assume a reference surrounding temperature, commonly 30°C. When the installation environment runs hotter, insulation and copper or aluminum operate closer to thermal limits. Derating applies a correction factor so protective devices, terminations, and cable jackets remain within permissible temperature rise.

2) Typical design ambient values

For indoor electrical rooms, 30–35°C is often used for conservative sizing. Industrial spaces, attics, rooftops, and near-process equipment can exceed 40–50°C. In hot climates, peak summer conditions and ventilation limitations can push local ambient toward 55°C, especially in enclosed conduits or cable trays.

3) Understanding correction factors

Correction factors reduce allowable current as ambient increases. This calculator uses common 5°C bands and applies A = Abase × F. If your base ampacity is referenced at another ambient, it normalizes by dividing by the reference factor first, then applying the target factor for consistent results.

4) Insulation temperature ratings

Ratings such as 60°C, 75°C, and 90°C reflect insulation capability, not necessarily termination limits. Many lugs and breakers are limited to 75°C or 60°C depending on equipment and conductor size. Always size to the lowest applicable temperature rating in the termination path.

5) Rooftops and solar heating

Sun exposure can raise conductor temperature beyond measured air temperature. Rooftop raceways and metallic conduit can absorb radiant heat, causing additional thermal stress. When solar effects are significant, verify whether your governing standard requires adders, special rooftop tables, or installation-specific adjustments.

6) Combined effects in the field

Ambient correction is only one part of thermal design. Grouping, bundling, multi-conductor conduits, insulation in walls, and reduced airflow can further reduce ampacity. If multiple derating mechanisms apply, they are typically multiplied, and the most restrictive condition should govern your final allowable current.

7) Documentation for inspections

Projects benefit from traceable calculations. Record base ampacity source, reference ambient, selected rating, and the applied factor. This page exports CSV and PDF summaries to attach to submittals, QA checklists, and commissioning packages so reviewers can validate assumptions quickly.

8) Practical sizing workflow

Start with load current and continuous-load rules, select an initial conductor size from tables, apply ambient and other corrections, then confirm the derated ampacity exceeds design current with margin. Re-check voltage drop and short-circuit ratings, and confirm terminations match the selected temperature rating.

FAQs

1) What does ambient derating change?

It adjusts the allowable current so conductor temperature stays within insulation and termination limits when the surrounding air is hotter than the reference condition.

2) Why is 30°C commonly used as reference?

Many ampacity tables are published for 30°C ambient, making it a practical baseline for comparing correction factors and ensuring consistent calculations.

3) Should I pick the highest insulation rating available?

Not always. Equipment terminations may be limited to 60°C or 75°C. Use the lowest applicable temperature rating across conductor, terminals, and devices.

4) Can I apply a safety margin here?

Yes. The optional margin reduces the final allowable ampacity after correction. It helps account for uncertain ambient peaks, airflow limits, and construction variability.

5) What if my ambient is outside the supported table?

The calculator blocks results to prevent misleading values. Confirm the correct standard tables for your jurisdiction, or use manufacturer engineering data for extreme conditions.

6) Does this replace code compliance checks?

No. It supports estimation and documentation. Always verify with the governing electrical code, AHJ requirements, and product datasheets for final design approval.

7) Are solar and rooftop effects included automatically?

No. This tool uses air-temperature correction factors only. If rooftop adders or radiant heating rules apply, incorporate those adjustments separately per your standard.

Important: This tool is for estimation and documentation support. Always follow the authority having jurisdiction (AHJ) and manufacturer limits for your installation.

Use derating results to choose safer conductor sizes always.