Bolted Fault Current Calculator

Fast fault calculations for panels, switchgear, and feeders. Adjust X/R, motors, and cable runs easily. Download CSV or PDF results for your project files.

Calculator Inputs

Choose a method, enter values, then calculate to see results above.

Pick based on available site data.
Example: 0.415 for 415 V systems.
Use nameplate rating for accuracy.
Typical range: 4% to 8%.
Used to estimate peak making current.
Optional: add a simple percentage allowance.
Used for I²t estimate (e.g., 0.1 s).
Cable / Feeder Impedance
Per-phase values

Enter R and X per unit length. The calculator multiplies by length.

Match your cable data source.
Enter in the same basis as selected.
Typical LV cables: 0.03–0.2 ohm/km.
Often 0.06–0.15 ohm/km for LV.
Tip
If you only have cable impedance magnitude, estimate R and X using an X/R value.
Custom Thevenin Impedance
Ohms per phase

Use when a short-circuit study provides R and X directly.

Note
In this mode, transformer and cable fields are ignored.
Clear
Example Data Table

Use this as a starting point and replace values with your project inputs.

Case Method Voltage (kV) kVA %Z X/R Cable Sym. Fault (kA) Peak (kA)
1 Transformer only 0.415 1000 5.75 10 ≈ 24.1 ≈ 63.3
2 Transformer + cable 0.415 1000 5.75 10 0.05 km, R=0.08, X=0.09 ≈ 22.4 ≈ 59.0

Example outputs are approximate and depend on rounding.

Formula Used
1) Full-load current
IFL = (kVA × 1000) / (√3 × VLL)
VLL in volts, 3-phase systems.
2) Transformer impedance in ohms
Zbase = VLL2 / S
|Ztr| = Zbase × (Z% / 100)
S in VA (3-phase), |Z| per phase.
3) Split |Z| into R and X using X/R
R = |Z| / √(1 + (X/R)2)
X = (X/R) × R
4) Symmetrical bolted fault current
Ik = Vphase / |Ztotal|
Vphase = VLL / √3
Ztotal combines transformer and cable R+jX.
5) Peak making current (IEC-style approximation)
k = 1.02 + 0.98 × e(-3 × R/X)
ip = k × √2 × Ik
This is a simplified method for peak estimation.
How to Use This Calculator
  1. Select a method: transformer only, transformer plus cable, or custom Thevenin.
  2. Enter system voltage, transformer kVA, impedance, and X/R ratio.
  3. If using cable mode, input length and per-length R and X.
  4. Optionally add a motor contribution percentage and a duration for I²t.
  5. Click Calculate, then download CSV or PDF for records.

For equipment selection, always confirm with a qualified short-circuit study.

© 2026 Construction Electrical Tools — Bolted Fault Current Calculator

Related Calculators

After diversity calculatorSpare capacity calculatorDisplacement PF calculatorTrue PF calculatorPF penalty calculatorPF improvement calculatorPF target calculatorBranch voltage drop calculatorMotor voltage drop calculatorDrop limit calculator

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.