Cable Impedance Calculator

Model cable geometry to predict clean signal paths. Choose dielectric, units, and run length easily. Download CSV or PDF for audits and submittals fast.

Inputs
Choose cable type, then enter geometry and run details.
Cable & Dielectric
All models assume a uniform dielectric around conductors.
Geometry
Example: 1.00 mm for small coax.
Must be greater than inner diameter.
Tip: For real cables, Z0 can deviate due to braid, insulation shape, tolerances, and frequency effects. Use manufacturer data when available.
Run & Load (optional)
Requires nonzero frequency and length.
X is positive inductive, negative capacitive.
Example Data Table
Typical characteristic impedances vary by insulation and manufacturing tolerances.
Use case Cable style Typical Z0 Notes
RF feeders Coaxial 50 Ω Common for transmit/receive equipment.
Video distribution Coaxial 75 Ω Widely used for CCTV and video links.
Antenna feeds Twin-lead 300 Ω Low loss, sensitive to nearby objects.
Data cabling Twisted pair 100 Ω Typical balanced line for LAN systems.
Formulas Used
  • Coaxial line: Z0 = (60 / √εr) · ln(b/a), where a is inner radius, b is outer inner radius.
  • Two-wire line: Z0 = (120 / √εr) · acosh(D/(2r)), where r is wire radius and D is center spacing.
  • Per‑length parameters: Z0 = √(L′/C′), with L′ and C′ derived from geometry and εr.
  • Wave velocity: vp ≈ c/√εr, velocity factor ≈ 1/√εr.
  • Input impedance (lossless): Zin = Z0(ZL + jZ0tanβl)/(Z0 + jZLtanβl), β = 2πf/vp.
These equations assume a uniform dielectric and ignore conductor and dielectric losses.
How to Use This Calculator
  1. Select a cable type that matches your installation geometry.
  2. Choose a dielectric preset or enter a custom εr value.
  3. Enter diameters and spacing using your selected units.
  4. Provide run length to estimate delay and wavelength.
  5. Optionally enter frequency and load to compute Zin and VSWR.
  6. Export your saved history to CSV or create a PDF report.

Impedance planning for mixed‑use construction cabling

Consistent characteristic impedance reduces reflections and signal loss across long runs in buildings. This calculator estimates Z0 from geometry and dielectric constant, helping you align field selections with typical 50 Ω, 75 Ω, 100 Ω, and 300 Ω systems. Use it early to compare options before ordering reels, connectors, and termination hardware.

For quick checks, compare computed Z0 to your system target and keep connector families consistent. Mixing 50 Ω and 75 Ω components often causes ghosting, dropouts, and poor return loss. If TDR traces are available, confirm sections affected by splices, tight bends, or moisture during punchlist walks.

Geometry tolerance and installation reality

Small dimensional changes can shift Z0 noticeably. Coax depends on ln(b/a), so oval jackets, braid compression, or rework at bends can alter the effective ratio. For twin‑lead and balanced pairs, spacing and conductor diameter drive acosh(D/2r). Maintain gentle routing, avoid crushing, and protect spacing near clamps and trays.

Dielectric selection and velocity factor

The dielectric constant εr affects both impedance and propagation speed. Lower εr increases Z0 and raises velocity factor, reducing delay per meter. Foam insulations often provide higher velocity than solid polymers, while higher‑εr materials increase capacitance. Capture the specified insulation type from cut sheets to match commissioning assumptions.

Frequency, wavelength, and reflection risk

When run length becomes a meaningful fraction of wavelength, mismatches create standing waves. The optional load model reports Zin and VSWR using the lossless transmission‑line relationship, which is useful for predicting tuning sensitivity at RF and high‑speed signaling frequencies. For low‑frequency control wiring, Z0 matters less than resistance and shielding.

Documentation outputs for QA and handover

Use the CSV export to log assumptions and compare alternatives across floors or risers. The PDF report packages the latest calculation plus session history for submittals, audits, sitewide records, and troubleshooting notes. Pair these exports with labeling details, connector part numbers, and test measurements (TDR or network certification) to close the loop from design to verification.

FAQs

1) What does characteristic impedance mean on a jobsite?

It is the cable’s natural impedance for fast signals. Matching it with connectors and terminations minimizes reflections, improves signal integrity, and reduces intermittent issues during commissioning and turnover.

2) Why does εr change the result so much?

εr changes capacitance and wave velocity. A higher εr lowers Z0 and slows propagation, increasing delay. Using the correct insulation type from the cable datasheet keeps estimates aligned with installed performance.

3) Should I enter shield thickness for coax?

No. This model uses the inner conductor diameter and the inner diameter of the outer conductor. Shield thickness mainly affects loss and mechanical strength, not the primary Z0 geometry ratio.

4) When is the input‑impedance (Zin) section useful?

Use it when frequency and length are significant, such as RF feeders, video distribution, or high‑speed data. It helps predict mismatch behavior with a specified load and highlights likely VSWR issues.

5) Does the calculator include attenuation or skin effect?

No. Results assume a lossless line for Zin and ideal geometry for Z0. Real cables have frequency‑dependent losses and tolerances. Validate with manufacturer specs and field testing when accuracy is critical.

6) How can I use outputs for submittals?

Export CSV to document assumptions and comparisons, then generate a PDF for the record set. Attach cable datasheets, routing notes, and test results to provide traceable evidence for quality control.

Saved Session History
Download CSV
Up to 50 recent calculations are retained in this browser session.
Time Cable εr Geometry Length Freq Z0 Zin VSWR
No saved calculations yet.

Related Calculators

After diversity calculatorSpare capacity calculatorDisplacement PF calculatorTrue PF calculatorPF penalty calculatorPF improvement calculatorPF target calculatorBranch voltage drop calculatorMotor voltage drop calculatorDrop limit calculator