UK Heat Loss Calculator

Calculate heat loss per room using UK-ready methods and realistic assumptions for winter design. Input U-values, areas, ΔT, infiltration rates, and ventilation recovery percentages or efficiencies. Include thermal bridging with Y-values and construction age-based presets for walls roofs. Compare radiator sizes and boiler load with margin. Export results as CSV or PDF for records.

Building & Method Settings

Typical UK winter design around -1 °C to -3 °C.
Adds headroom for warm-up and uncertainties.
Infiltration at design: 0.4–1.0 typical; older homes higher.
If no MVHR, leave at 0.
Common default where details are reasonably good.
For display in notes only.

Rooms & Envelope Inputs

Room Length (m) Width (m) Height (m) Setpoint (°C) Wall area (m²) Wall U (W/m²·K) Window area (m²) Window U Door area (m²) Door U Roof/Ceiling area (m²) Roof U Floor area (m²) Floor U Actions
Tip: If room shares elements internally, reduce corresponding exposed areas.

Results

0.00 kW
Total design heat loss (with margin)
0 W/K
Fabric + thermal bridge heat loss coefficient
0 W/K
Ventilation / infiltration heat loss coefficient
ΔT = 0 K
Overall design temperature difference
Room Area (m²) Volume (m³) ΔT (K) H_fabric (W/K) H_tb (W/K) H_vent (W/K) Design loss (W) With margin (W)
Totals 0 0 0 0 0 0 0
Note: Use ΔT50 radiator charts or manufacturer ratings to select emitters.

Example Data

Click “Add Room” twice and copy the example figures.

RoomLWHSetpoint Wall AWall UWin AWin U Door ADoor URoof ARoof U Floor AFloor U
Lounge4.83.82.421 320.3061.40 1.91.8018.20.18 18.20.22
Bedroom3.63.22.419 240.3031.40 01.8011.50.18 11.50.22

Formula Used

Fabric loss (per room): H_fabric = Σ(U_i × A_i)

Thermal bridge (approx.): H_tb = y × A_exposed where A_exposed = A_walls + A_windows + A_doors + A_roof + A_floor

Ventilation/infiltration: H_vent = 0.33 × n_eff × V, where n_eff = ACH × (1 − η_MVHR)

Design heat loss: Q = (H_fabric + H_tb + H_vent) × ΔT, with ΔT = T_set − T_out

With margin: Q_margin = Q × (1 + margin%)

0.33 ≈ ρ_air × c_p / 3600 with ρ≈1.2 kg/m³, c_p≈1000 J/(kg·K).

How to Use

  1. Set the external design temperature appropriate for your UK locality.
  2. Enter ACH and any MVHR efficiency, else leave defaults.
  3. Click “Add Room”, fill geometry, areas, and U-values for each surface.
  4. Use setpoint temperatures per room; living spaces often 20–21 °C.
  5. Press “Calculate” to see per-room and total heat losses.
  6. Adjust the safety margin to match commissioning intentions.
  7. Export results to CSV or PDF for records or quotations.

FAQs

Recent UK regs target about 0.18–0.25 for roofs, 0.22 floors, 0.26–0.30 walls, 1.2–1.6 modern windows. Use your as-built specification if known.

-1 °C is typical nationally; colder northern/continental exposures may use -3 °C or below. Local guidance or CIBSE design data may refine this value.

Party walls or internal partitions typically do not contribute to external heat loss. Exclude their areas or assign negligible U-values when shared with similarly heated spaces.

This tool uses a y-value approximation. Detailed assessments use ψ-values per junction and lengths. If you have them, sum ψ×L and add to H_fabric instead.

Yes. Effective ACH is scaled by (1 − efficiency). For example, 80% recovery at 0.6 ACH behaves like 0.12 ACH for heat loss purposes, assuming balanced flows.

10–20% is common for radiator selection. Larger margins increase responsiveness but may reduce condensing efficiency for modulating systems if emitters are oversized.

Related Calculators

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.