Negative Air Unit Count Calculator

Plan clean demolition containment with confidence today. Size negative air units from volume and ACH. Reduce dust spread, protect occupants, and meet project requirements.

Calculator Inputs

Use room dimensions, target air changes, and equipment airflow to estimate how many negative air units are needed for containment ventilation.

Unit System
Choose the measurement system for all fields.
Length
Containment length.
Width
Containment width.
Height
Containment height.
Target ACH
Air changes per hour you want to achieve.
Unit Airflow
Rated airflow for one unit.
Safety Factor
Covers filter loading and performance losses.
Leakage Factor
Covers door openings and imperfect sealing.
Target Pressure (Pa)
Optional planning value for documentation.
Notes
Optional: save assumptions with your report.
Reset
Tip: If you are unsure, start with ACH 6-12 and set safety at 1.20.

Example Data Table

Sample scenario to help validate your inputs.
Length (ft) Width (ft) Height (ft) ACH Unit Airflow (CFM) Safety Leakage Volume (ft³) Adjusted Airflow (CFM) Units Needed
20 15 10 6 2000 1.20 1.00 3000 360 1

Formula Used

1) Containment Volume
Imperial: V = L × W × H (ft³)
Metric: V = L × W × H (m³)

2) Required Airflow from ACH
Imperial: Q = (V × ACH) ÷ 60 (CFM)
Metric: Q = V × ACH (m³/h)

3) Adjusted Airflow
Qadj = Q × Safety × Leakage

4) Unit Count
Units = ceiling(Qadj ÷ UnitAirflow)
Rounded up so the target ventilation is achieved.

How to Use This Calculator

  1. Pick a unit system and enter containment dimensions.
  2. Set your target ACH based on scope and cleanliness needs.
  3. Enter the rated airflow of one negative air unit.
  4. Apply a safety factor for filter loading and losses.
  5. Add a leakage factor if openings or leakage are expected.
  6. Click Calculate to get the required unit count.
  7. Use the download buttons to save a CSV or PDF report.

Article

1) Purpose of negative air ventilation

Negative air units help keep dust and contaminants inside a containment by exhausting air through filtration and directing flow inward at openings. Correct unit counts reduce migration risk to adjacent areas, improve worker comfort, and support cleaner handoff to finishing trades during controlled demolition and renovation. Sizing also helps plan power needs and equipment placement.

2) Volume drives the baseline airflow

The first step is enclosure volume (V = L × W × H). In imperial units, baseline airflow is Q = (V × ACH) ÷ 60. A 20 × 15 × 10 ft zone is 3,000 ft³. At 6 ACH, baseline airflow is 300 CFM before allowances. In metric, Q = V × ACH using m³/h.

3) Choosing an ACH target

ACH is a planning target that links activity intensity to ventilation. Many teams start between 6 and 12 ACH, increasing for higher dust loads, frequent debris movement, or stricter cleanliness expectations. For sensitive areas, extra ACH can be paired with better sealing to stabilize conditions. Reassess after the first shift based on observed dust and traffic.

4) Adjusting for real performance

Rated airflow can drop as filters load, bends add losses, and long ducts raise resistance. The safety factor covers performance losses, while the leakage factor covers door traffic, imperfect sealing, and temporary openings. For the 300 CFM baseline example, using 1.20 safety and 1.00 leakage gives 360 CFM adjusted demand.

5) Unit selection and verification

Divide adjusted airflow by unit capacity and round up. With a 2,000 CFM unit, 360 CFM requires one unit; with a 250 CFM unit, it requires two. Splitting airflow across multiple units can add redundancy and simplify maintenance. After setup, confirm directional airflow at entry points and log filter changes, readings, and notes so daily checks remain consistent.

FAQs

1) What does this calculator estimate?

It estimates how many negative air units you need to meet a target ventilation rate based on enclosure volume, desired ACH, and the airflow rating of each unit, with optional safety and leakage adjustments.

2) Which ACH value should I use?

Use a planning ACH that matches task intensity. Light work may use 6 ACH, while heavy dust generation can justify 10 to 12 ACH. When unsure, start higher and refine after stable site observations.

3) Why do I need safety and leakage factors?

Rated airflow can drop with filter loading and duct resistance. Leakage and door openings increase air demand. These factors help avoid under-sizing and improve reliability during peak activity.

4) Does airflow guarantee negative pressure?

No. Negative pressure depends on enclosure tightness, make-up air pathways, and exhaust location. Airflow sizing supports ventilation targets, while pressure stability requires good sealing, controlled openings, and consistent exhaust performance.

5) Should I use one large unit or multiple units?

Multiple units can provide redundancy and flexible staging. If one unit fails, others can maintain partial ventilation. Multiple exhaust points can also help balance airflow, depending on containment geometry and duct routing.

6) How do I enter metric airflow?

Select Metric to use meters and m³/h. Enter unit airflow in m³/h, not per minute. The calculator uses Q = Volume × ACH for metric, matching the hourly basis of ACH.

7) What should I include in the report?

Capture dimensions, ACH target, unit ratings, factors used, calculated unit count, filter configuration, and site notes. Exporting the CSV or PDF helps keep a consistent record for supervisors and quality documentation.

Related Calculators

TEM Sample Cost CalculatorPCM Sample Cost CalculatorPLM Lab Cost CalculatorChain Of Custody CalculatorSampling Labor Hours CalculatorSampling Travel Cost CalculatorSampling Total Cost CalculatorRisk Assessment Score CalculatorMaterial Risk Rating CalculatorFriability Risk Calculator

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.

?>