Plan electrical capacity with clear load inputs. Apply demand, diversity, efficiency, and power factor values. Get a standard size recommendation for safer installations today.
Demand_kW = Connected_kW × DemandFactor ÷ DiversityFactorkW_growth = Demand_kW × (1 + Growth%/100)kVA_base = kW_growth ÷ (PowerFactor × Efficiency)kVA_required = kVA_base ÷ (1 − (Harmonic% + Temp%)/100)I = kVA×1000 ÷ (√3×V) (three-phase) or I = kVA×1000 ÷ V (single-phase)
Temporary and permanent construction power often changes weekly. Undersized transformers can overheat, trip protection, and interrupt critical works such as concrete placement, dewatering, and commissioning. Oversizing increases capex, transport weight, and no-load losses. This calculator balances realistic demand with practical safety margins using demand, diversity, growth, and derating inputs.
Connected load totals from panel schedules rarely operate at once. Demand factor reflects simultaneous usage, while diversity accounts for how grouped loads share spare capacity. For example, welfare facilities and lighting may be steady, while welders and small tools are intermittent. Applying both factors produces a more defendable demand kW for sizing.
Transformers are rated in kVA, not kW. Low power factor increases kVA needed for the same real power. Efficiency accounts for conversion losses; using realistic values prevents optimistic sizing. Where possible, use measured PF from meters or manufacturer data for VFD-driven and UPS-supported systems.
Non-linear loads (VFDs, rectifiers, UPS) raise heating through harmonics, and high ambient temperatures reduce thermal headroom. A combined derating allowance converts base kVA into a required kVA that better matches site conditions. Always cross-check enclosure ventilation, clearance, and duty cycle.
Example data: Connected load 120 kW, demand 0.80, diversity 0.90, PF 0.90, efficiency 0.98, growth 20%, harmonic derating 5%, temperature derating 5%, voltage 415 V, three-phase. The calculator returns a derated requirement near 185 kVA and selects a 200 kVA standard rating.
Use kVA for transformer selection. Convert from kW using power factor and efficiency because low power factor increases apparent power demand and current.
Many mixed sites use 0.70–0.90 depending on simultaneity. Base it on work sequencing, shift patterns, and whether heavy equipment runs together.
In this calculator, a lower diversity factor represents less sharing of spare capacity across groups, so the adjusted demand kW increases to avoid undersizing.
Harmonics add heating and can reduce usable capacity. Apply harmonic derating for VFDs, UPS systems, and large rectifier loads, then verify with equipment specifications.
No. It estimates steady-state capacity. Motor starting currents, protection coordination, fault levels, and voltage drop should be checked separately for compliance and reliability.
Common allowances range from 10% to 30% for evolving sites. Use higher values when future trades, temporary plants, or additional cabins are expected.
Choose the next standard rating at or above the derated requirement, then confirm physical constraints, voltage class, tap settings, and utility or generator compatibility.
| Scenario | Connected kW | Demand | Diversity | PF | Eff | Growth | Derating | Voltage | Phase | Recommended Size |
|---|---|---|---|---|---|---|---|---|---|---|
| Site offices + lighting | 55 | 0.85 | 0.95 | 0.92 | 0.98 | 15% | 6% | 230 | Single | 75 kVA |
| Mixed temporary works | 120 | 0.80 | 0.90 | 0.90 | 0.98 | 20% | 10% | 415 | Three | 200 kVA |
| Motor-heavy pumping | 180 | 0.75 | 0.85 | 0.88 | 0.97 | 25% | 12% | 480 | Three | 400 kVA |
Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.