Find cable sizes for inverters and DC loads. Review voltage loss, ampacity, and installation factors. Build dependable low-voltage systems with stronger electrical confidence today.
1) Voltage drop area requirement
Adrop = (2 × L × I × ρ) ÷ Vdrop
Where A is cable area in mm², L is one-way length in meters, I is current per run in amps, ρ is conductor resistivity, and Vdrop is the allowed drop in volts.
2) Allowed voltage drop
Vdrop = 24 × (allowed drop % ÷ 100)
This converts the chosen percentage into volts for a 24V battery system.
3) Corrected ampacity
Ampacitycorrected = Base ampacity × material × installation × ambient × insulation
The selected cable must meet both the voltage-drop requirement and the corrected ampacity requirement.
4) Design current
Idesign = max(continuous × growth factor, peak current) × safety factor
This allows the calculator to account for future expansion and conservative sizing.
| Continuous Current | Peak Current | Length | Drop Limit | Material | Suggested Size |
|---|---|---|---|---|---|
| 40 A | 60 A | 2 m | 3% | Copper | 6.00 mm² |
| 80 A | 120 A | 3 m | 3% | Copper | 25.00 mm² |
| 120 A | 150 A | 4 m | 2% | Copper | 50.00 mm² |
| 80 A | 100 A | 4 m | 3% | Aluminum | 50.00 mm² |
These examples are illustrative only. Local codes, connector limits, and manufacturer data should always be checked before final installation.
Low-voltage systems are sensitive to voltage drop. Even a small resistance causes a noticeable loss, so current-heavy loads often need surprisingly large conductors.
Yes, if the formula doubles it internally. This calculator uses one-way distance, then applies a round-trip path because current leaves and returns.
Use both. The calculator compares future-adjusted continuous current against peak demand, then sizes from the larger value with your safety margin.
Aluminum has higher electrical resistance and lower ampacity for the same cross-section. A larger area is usually required to match copper performance.
Many designers target 2% to 3% for battery and inverter circuits. Critical electronics may need tighter limits, while non-sensitive loads can allow more.
Treat it as a guide only. Final fuse selection must also match equipment requirements, inrush behavior, connector ratings, and applicable wiring standards.
Parallel runs help when one cable becomes too large or impractical. They should be identical in length, size, termination quality, and routing.
No. It is a practical sizing tool for planning and comparison. Final designs should be checked against local codes and manufacturer recommendations.
Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.