Model fault current at your selected electrical bus. Compare source, transformer, cable, and motor effects. Review calculated duties instantly for faster coordination decisions today.
The page stays single-column, while the input area uses 3 columns on large screens, 2 on medium screens, and 1 on mobile.
The sample below shows a low-voltage bus with transformer and feeder impedance included.
| Item | Sample value | Unit | Notes |
|---|---|---|---|
| Bus voltage | 0.48 | kV | Three-phase line-to-line bus |
| Voltage factor | 1.05 | - | Assumes slightly elevated operating voltage |
| Source short-circuit level | 500 | MVA | Utility/source stiffness |
| Transformer size | 1500 | kVA | Secondary tied to the selected bus |
| Transformer impedance | 5.75 | % | Nameplate value |
| Cable length | 120 | ft | Using per 1000 ft basis |
| Cable R / X | 0.018 / 0.015 | ohm per 1000 ft | Feeder impedance data |
| Motor contribution | 1.8 | kA | Initial motor backfeed estimate |
| Symmetrical RMS current | 25.297 | kA | Calculated bolted fault current |
| Total available current | 27.097 | kA | Includes motor contribution |
| Fault duty | 22.528 | MVA | At the selected bus |
| Peak current estimate | 50.826 | kA | Based on the equivalent X/R ratio |
Zsource = V² / MVAscZtx = (Z% / 100) × (V² / MVAtx)Rcable = Rrate × Length and Xcable = Xrate × Length using the selected basisRtotal = ΣR, Xtotal = ΣX, Ztotal = √(Rtotal² + Xtotal²)Ibf = (V × Voltage Factor) / (√3 × Ztotal)Itotal = Ibf + ImotorFault MVA = √3 × V × Itotalκ = 1.02 + 0.98e-3/(X/R), then ipeak = κ × √2 × IbfVoltage is entered in kV line-to-line. Current results are shown in kA. Impedance is handled in ohms on the chosen bus base.
Bolted fault current is the maximum available current when conductors are shorted together with negligible fault resistance. It helps determine interrupting and withstand duties for electrical equipment.
The source sets upstream strength, while transformer impedance often limits current heavily on the secondary bus. Using both gives a more realistic available fault level.
Yes. Large motors can feed current back into a nearby fault for the first few cycles. That extra contribution can affect interrupting rating checks and protective device coordination.
No. This page is arranged for three-phase bolted faults using equivalent positive-sequence impedance. Single-line-to-ground studies need sequence networks and different fault equations.
Enter the nominal line-to-line voltage at the bus where you want the fault current. For low-voltage switchboards, that is often 0.48 kV or 0.415 kV.
It is an engineering estimate based on the equivalent X/R ratio. It is useful for screening studies, but final equipment verification should follow the governing standard and manufacturer data.
Yes. Added feeder resistance and reactance increase total impedance, which lowers the symmetrical RMS fault current seen at the downstream bus.
Compare the calculated duty against the breaker interrupting rating and any required withstand or peak limits. Also confirm coordination, voltage class, and the applicable standard for your system.
Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.