Bolted Fault Current Calculator

Model fault current at your selected electrical bus. Compare source, transformer, cable, and motor effects. Review calculated duties instantly for faster coordination decisions today.

Enter system data

The page stays single-column, while the input area uses 3 columns on large screens, 2 on medium screens, and 1 on mobile.

Advanced electrical model
Example: 0.48, 4.16, 11, 33
Use 1.00 to 1.10 for a realistic operating range.
Available fault level seen at the source side.
Used to split source impedance into resistance and reactance.
Set to 0 if no transformer is included.
Typical values often range from 4% to 8%.
Used for peak-current estimation.
Choose the matching basis before entering feeder impedance.
Use ft with the first basis, or km with the second.
Ohm per 1000 ft or ohm per km.
Ohm per 1000 ft or ohm per km.
Use for busway, reactor, switchgear, or custom items.
Add any extra series reactance not captured elsewhere.
Approximate initial contribution from connected motors.
Used for the I²t thermal-duty indicator.

Example data table

The sample below shows a low-voltage bus with transformer and feeder impedance included.

Item Sample value Unit Notes
Bus voltage0.48kVThree-phase line-to-line bus
Voltage factor1.05-Assumes slightly elevated operating voltage
Source short-circuit level500MVAUtility/source stiffness
Transformer size1500kVASecondary tied to the selected bus
Transformer impedance5.75%Nameplate value
Cable length120ftUsing per 1000 ft basis
Cable R / X0.018 / 0.015ohm per 1000 ftFeeder impedance data
Motor contribution1.8kAInitial motor backfeed estimate
Symmetrical RMS current25.297kACalculated bolted fault current
Total available current27.097kAIncludes motor contribution
Fault duty22.528MVAAt the selected bus
Peak current estimate50.826kABased on the equivalent X/R ratio

Formula used

1. Source impedance
Zsource = V² / MVAsc
2. Transformer impedance
Ztx = (Z% / 100) × (V² / MVAtx)
3. Cable impedance
Rcable = Rrate × Length and Xcable = Xrate × Length using the selected basis
4. Total impedance
Rtotal = ΣR, Xtotal = ΣX, Ztotal = √(Rtotal² + Xtotal²)
5. Symmetrical bolted fault current
Ibf = (V × Voltage Factor) / (√3 × Ztotal)
6. Total available current
Itotal = Ibf + Imotor
7. Fault duty
Fault MVA = √3 × V × Itotal
8. Peak current estimate
κ = 1.02 + 0.98e-3/(X/R), then ipeak = κ × √2 × Ibf

Voltage is entered in kV line-to-line. Current results are shown in kA. Impedance is handled in ohms on the chosen bus base.

How to use this calculator

  1. Enter the line-to-line bus voltage in kV.
  2. Set a voltage factor that reflects expected operating voltage during the fault.
  3. Provide the available source short-circuit MVA and source X/R ratio.
  4. Enter transformer kVA, percent impedance, and X/R if a transformer feeds the bus.
  5. Select the cable basis, then enter feeder length and impedance values.
  6. Add any extra resistance or reactance from reactors, busway, or custom equipment.
  7. Estimate motor contribution if motors on the bus can backfeed the fault.
  8. Enter clearing time to review a simple I²t duty indicator.
  9. Press the calculate button to display results above the form.
  10. Use the CSV or PDF buttons to export the calculated summary.

FAQs

1) What is bolted fault current?

Bolted fault current is the maximum available current when conductors are shorted together with negligible fault resistance. It helps determine interrupting and withstand duties for electrical equipment.

2) Why are source and transformer values both needed?

The source sets upstream strength, while transformer impedance often limits current heavily on the secondary bus. Using both gives a more realistic available fault level.

3) Does motor contribution really matter?

Yes. Large motors can feed current back into a nearby fault for the first few cycles. That extra contribution can affect interrupting rating checks and protective device coordination.

4) Is this calculator for ground faults too?

No. This page is arranged for three-phase bolted faults using equivalent positive-sequence impedance. Single-line-to-ground studies need sequence networks and different fault equations.

5) Which voltage should I enter?

Enter the nominal line-to-line voltage at the bus where you want the fault current. For low-voltage switchboards, that is often 0.48 kV or 0.415 kV.

6) How accurate is the peak current estimate?

It is an engineering estimate based on the equivalent X/R ratio. It is useful for screening studies, but final equipment verification should follow the governing standard and manufacturer data.

7) Can longer cables reduce available fault current?

Yes. Added feeder resistance and reactance increase total impedance, which lowers the symmetrical RMS fault current seen at the downstream bus.

8) How should I use the result for breaker selection?

Compare the calculated duty against the breaker interrupting rating and any required withstand or peak limits. Also confirm coordination, voltage class, and the applicable standard for your system.

Related Calculators

generator fault current calculatorfault loop impedance calculatormaximum fault current calculator

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.