Calculated Result
The result panel appears here after you submit the form.
Calculator Inputs
Formula Used
Single-phase AC current: I = P × 1000 ÷ (V × PF × η)
Three-phase AC current: I = P × 1000 ÷ (√3 × V × PF × η)
DC current: I = P × 1000 ÷ (V × η)
Adjusted design current: Iadj = I × demand factor × continuous factor × spare factor
Minimum conductor ampacity: Icond = Iadj ÷ (ambient derating × grouping derating)
Recommended device rating: next standard size at or above Iadj
Required interrupting capacity: available fault current × fault margin
All percentage inputs are converted into decimal factors during the calculation.
How to Use This Calculator
- Select whether you want to derive current from power or enter current directly.
- Choose the system type and the protective device family.
- Fill in power, voltage, power factor, and efficiency if you are using the power method.
- Enter demand, continuous loading, spare margin, and conductor derating factors.
- Enter inrush multiplier to guide trip-characteristic selection.
- Provide available fault current and a fault margin to review interrupting duty.
- Press Calculate Protection to show the result above the form.
- Export the result as CSV or PDF after reviewing the design notes.
Example Data Table
This sample shows one typical three-phase motor feeder review.
| Input or Output | Value | Notes |
|---|---|---|
| System Type | Three-phase AC | Motor feeder example |
| Load Power | 18.5 kW | Derived current method |
| Voltage / PF / Efficiency | 415 V / 0.88 / 92% | Input assumptions |
| Demand / Continuous / Spare | 100% / 125% / 10% | Planning factors |
| Ambient / Grouping Derating | 90% / 85% | Combined derating 0.765 |
| Inrush / Fault Current | 6× / 18 kA | Trip and interrupting review |
| Calculated Operating Current | 31.79 A | From three-phase power formula |
| Adjusted Design Current | 43.71 A | After demand, continuous, and spare factors |
| Recommended OCPD / Curve | 50 A / C curve | Next listed rating above design current |
| Recommended Conductor / Interrupting | 57.14 A / 25 kA | Derating and fault margin considered |
FAQs
What does this overcurrent protection calculator estimate?
It estimates operating current, adjusted design current, conductor ampacity, a suggested protective rating, trip behavior, and an interrupting-capacity target from your entered load and derating assumptions.
Can I use it for motors and feeders?
Yes. It supports direct-current entry or power-based current estimation. Motor loads benefit from the inrush input, while feeder checks benefit from demand, spare, and derating factors.
Does it replace electrical code compliance?
No. It is a planning and review tool. Final device selection must still follow your adopted code, coordination study, conductor rules, and manufacturer data.
How is the recommended rating selected?
The tool calculates an adjusted design current and then chooses the next higher listed device size from the selected regional standard series.
Why is conductor ampacity sometimes higher than device rating?
Ambient and grouping derating reduce usable conductor capacity. When derating is strong, the conductor may need a larger ampacity even if the breaker size seems modest.
What is interrupting capacity?
Interrupting capacity is the maximum fault current a protective device can safely clear. The tool applies your fault margin, then selects the next standard available rating.
Why does the trip curve recommendation change?
Higher inrush multipliers need slower magnetic response to avoid nuisance trips. That is why heavier-starting equipment tends to need curves such as C, D, or K.
Can I export the results?
Yes. After calculation, use the CSV export for spreadsheets or the PDF button for a printable summary of the displayed result table.