Match conductors to load, length, and derating. Check drop, breaker, and ampacity fast. Build dependable cable selections for practical electrical projects.
| Load | Phase | Voltage | Length | Material | Insulation | Suggested Size |
|---|---|---|---|---|---|---|
| 15 kW pump | Three | 415 V | 35 m | Copper | XLPE | 10 mm² |
| 25 kW motor | Three | 415 V | 45 m | Copper | XLPE | 16 mm² |
| 8 kW heater | Single | 230 V | 28 m | Copper | PVC | 16 mm² |
| 60 A feeder | Three | 415 V | 70 m | Aluminum | XLPE | 50 mm² |
These rows are illustrative examples. Final selections should follow site standards, local regulations, and manufacturer data.
The calculator first determines the operating current, adds design margin, applies derating, then selects the smallest standard cable size meeting ampacity and voltage drop targets.
It estimates a practical cable cross-sectional area using load current, installation derating, voltage drop, and a safety margin. It then maps the result to a standard cable size.
Motors and many real loads draw more current than ideal power alone suggests. Power factor and efficiency help convert input power into a more realistic current value.
A cable may carry current safely but still lose too much voltage over distance. Increasing conductor area reduces resistance and keeps terminal voltage within acceptable limits.
Grouping factor accounts for nearby loaded cables heating each other. More grouped circuits usually reduce usable ampacity, so larger cables may be required.
No. It is a practical starting point. Final breaker selection should also consider short-circuit level, protective coordination, inrush behavior, and applicable electrical codes.
Yes, but aluminum usually needs a larger cross-section for the same duty. It also has different installation, termination, and corrosion considerations.
No. It helps with engineering estimation and comparison. Always verify the result against local standards, equipment ratings, manufacturer tables, and project specifications.
Long routes, hot ambient conditions, grouped circuits, low allowable voltage drop, or motor starting requirements can all push the selection upward.
Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.