Check insulation aging using timed resistance readings. Compare one minute and ten minute values confidently. Guide maintenance decisions with fast results and practical insight.
Use one-minute and ten-minute insulation resistance values to estimate polarization behavior, compare against a target, and document the test outcome.
These sample values show how the ratio changes with insulation response over time.
| Equipment | 1-Min Resistance | 10-Min Resistance | PR | Condition |
|---|---|---|---|---|
| Motor A | 120 MΩ | 300 MΩ | 2.50 | Good |
| Transformer B | 80 MΩ | 100 MΩ | 1.25 | Fair |
| Cable C | 65 MΩ | 58 MΩ | 0.89 | Poor |
Polarization Ratio = Resistance at 10 minutes ÷ Resistance at 1 minute
Resistance Increase = Resistance at 10 minutes − Resistance at 1 minute
Increase Percentage = ((Resistance at 10 minutes − Resistance at 1 minute) ÷ Resistance at 1 minute) × 100
The polarization ratio compares the insulation resistance measured after ten minutes with the value measured after one minute during a DC insulation test. Higher values usually show stronger absorption and polarization effects, while lower values can point to contamination, moisture, leakage, or insulation aging.
It measures how insulation resistance changes between one minute and ten minutes during a DC test. The ratio helps indicate dryness, cleanliness, and polarization behavior.
A higher ratio often means resistance continues rising as polarization develops. That pattern usually suggests healthier insulation than a flat or falling response.
Direct comparison can be misleading because insulation resistance changes with temperature. Trend results only after using a consistent method or applying accepted temperature correction practices.
A value below one means the ten-minute resistance is lower than the one-minute value. That can indicate moisture, contamination, surface leakage, or unstable testing conditions.
No. It should be reviewed with equipment history, temperature, test voltage, cleaning condition, and other insulation tests for a stronger engineering judgment.
PR uses ten-minute and one-minute resistance values. DAR uses an earlier short-time reading, often sixty seconds divided by thirty seconds, to assess early absorption behavior.
It is commonly used for motors, generators, transformers, switchgear, and cable systems where insulation condition trending supports preventive maintenance programs.
Export after checking the entered values, units, and interpretation notes. Saved records are useful for maintenance reports, asset histories, and trend reviews.
Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.