The calculator reports available net positive suction head (NPSHa) and compares it to the pump requirement (NPSHr). Cavitation risk increases when NPSHa approaches or drops below NPSHr.
-
Reservoir static head method:
NPSHa = Patm/(ρg) + z − hL − Pv/(ρg) -
Suction flange pressure method:
NPSHa = Psuc,abs/(ρg) + hV − hL − hextra − Pv/(ρg) - Velocity head (auto option): hV = V2/(2g), where V = Q/A and A = πD²/4
- Margin: Margin = NPSHa − NPSHr
Tip: Many designs target at least about 1 m margin and 10% over NPSHr. Always follow vendor and project standards.
- Select a method that matches your data (reservoir or suction pressure).
- Enter fluid density or specific gravity, then set atmospheric pressure.
- Provide vapor pressure directly, or use the water temperature option.
- Enter static head and suction losses based on your piping and fittings.
- Enter the pump NPSHr value at your operating flow.
- For velocity head, either auto-calculate from flow and diameter or input it.
- Press Check NPSH to see margin and cavitation risk.
- Use CSV or PDF export to share results with your team.
| Method | ρ (kg/m³) | Patm (kPa) | Pv (kPa) | z (m) | hL (m) | NPSHr (m) | NPSHa (m) | Margin (m) |
|---|---|---|---|---|---|---|---|---|
| Reservoir | 998 | 101.325 | 3.17 | 2.0 | 1.2 | 3.0 | ≈ 6.85 | ≈ 3.85 |
| Suction flange | 1000 | 101.325 | 2.34 | 0.0 | 0.8 | 4.0 | ≈ 6.20 | ≈ 2.20 |
Example values are illustrative. Use your measured pressures, temperatures, and losses for accurate checks.
1) Why NPSH exists in pump design
Cavitation begins when local absolute pressure falls to the liquid’s vapor pressure, forming vapor bubbles that collapse as pressure recovers. The net positive suction head (NPSH) framework converts key pressures and elevations into a head balance, making cavitation checks consistent across sites and fluids.
2) What the calculator reports
This tool calculates NPSH available (NPSHa) and compares it with the pump’s required NPSH (NPSHr) from the vendor curve. It also shows the margin in meters and percent, plus supporting terms such as atmospheric head and vapor head.
3) Reservoir method inputs and meaning
Use the reservoir method when suction comes from a vented tank or sump. Atmospheric pressure adds a large positive head term, static head (z) can help or hurt, losses subtract, and vapor pressure subtracts. A negative z represents suction lift and strongly reduces NPSHa.
4) Suction pressure method for field measurements
Use the suction pressure method when you have a pressure reading near the pump suction. Enter the pressure type correctly: gauge readings must be converted to absolute using atmospheric pressure. Add extra loss head if the gauge tap is upstream of the impeller eye.
5) Vapor pressure rises rapidly with temperature
Vapor pressure is a dominant driver of cavitation risk. For water, approximate saturation vapor pressure is about 2.34 kPa at 20 °C, 3.17 kPa at 25 °C, 19.9 kPa at 60 °C, and 47.4 kPa at 80 °C. Higher vapor pressure reduces NPSHa directly.
6) Velocity head and suction sizing
Velocity head is V²/(2g). It increases with higher flow and smaller suction diameter. Although often below one meter, it can be significant in compact systems. Keeping suction velocity moderate reduces friction losses and improves NPSH margin.
7) Interpreting margin and risk flags
A positive margin means NPSHa exceeds NPSHr. The calculator labels “Caution” when margin is small and “High cavitation risk” when margin is negative. Many projects target at least ~1 m margin and ≥10% above NPSHr, but standards vary.
8) Practical ways to improve NPSH
Increase suction level, lower the pump, or pressurize the suction vessel to raise absolute pressure head. Reduce suction losses by shortening piping, increasing diameter, minimizing fittings, cleaning strainers, and avoiding sharp entrances. Lower fluid temperature when feasible, or select a pump with lower NPSHr at the duty point.
1) What is the difference between NPSHa and NPSHr?
NPSHa is what your system provides at the pump inlet. NPSHr is what the pump needs to avoid excessive cavitation at a specific flow. You want NPSHa to exceed NPSHr with margin.
2) Should I use absolute or gauge suction pressure?
Enter the type you actually measured. If you measured gauge pressure, the tool converts it to absolute using atmospheric pressure. Cavitation checks must use absolute pressure because vapor pressure is an absolute threshold.
3) How do I estimate suction losses hL?
Sum pipe friction and fittings losses from the suction source to the pump flange. Use your preferred method and include strainers and valves. Underestimating hL is a common reason NPSH margins look better than reality.
4) Why does warm water cavitate more easily?
Warm liquids have higher vapor pressure. Because vapor pressure subtracts from NPSHa, increasing temperature reduces the available margin. Small temperature increases can create large vapor pressure changes, especially above about 50 °C.
5) Does velocity head always help NPSH?
Velocity head is a positive term in the suction pressure method, but high velocity usually comes with higher friction losses and noise. In practice, sizing the suction to keep velocity moderate often improves total NPSH margin.
6) What margin should I aim for?
There is no single universal value. Many designs aim for roughly 1 m minimum and at least 10% above NPSHr. Always follow pump vendor guidance, project specifications, and consider uncertainties in loss estimates.
7) If margin is negative, what should I change first?
Start by checking data: vapor pressure, pressure type, and loss estimates. Then reduce suction losses by cleaning strainers and improving piping. If the system is fixed, lower the pump elevation, pressurize suction, or choose a pump with lower NPSHr.