After Diversity Calculator

Turn connected load into realistic maximum demand. Pick percentage or factor, include power and current. Download clean summaries, share with teams and clients fast.

Calculator Inputs

Use either a load list or a single connected-load value.
Reset

You can compute from kW, kVA, or current.
Used for kW-kVA conversion and current estimate.
Current is estimated at this voltage level.
Connected load source
Choose load list for detailed inputs, or enter one value.
Interpreted using the selected input unit above.
Tip: If you have multiple circuits or equipment, use the load list. It improves transparency and makes exports clearer.
Load list
Load name Value (kW) Note (optional)
Values are summed using the selected input unit. For current inputs, each row is current at the entered voltage and phase.
Pick the style used on your project/spec.
After diversity kW = connected kW × (diversity/100).
After diversity kW = connected kW ÷ factor.
Multiplies the diversified demand (0.10-1.50).
Adds headroom for future load increases.
These are typical starting values; verify requirements.
Results appear above this form after submission.

Example Data Table

These sample values show how connected load reduces after diversity.

Area / Circuit Connected (kW) Diversity (%) After diversity (kW) Comment
Lighting & small power 18.00 80 14.40 Typical non-simultaneous use.
HVAC package units 22.00 90 19.80 Often high coincidence in hot months.
Lift & fire pump 12.00 100 12.00 Treat critical loads as continuous.
Total 52.00 46.20 Used for feeder sizing checks.
You can replicate this in the load list by setting the input unit to kW and adding each row.

Formula Used

A) Diversity percentage (common site approach)
After Diversity (kW) = Connected (kW) × (Diversity% ÷ 100)
This approach treats diversity as a fraction of connected load. It's widely used for quick maximum-demand estimates.
B) Diversity factor (traditional definition)
After Diversity (kW) = Connected (kW) ÷ Diversity Factor
Here, the factor is >= 1. Higher values imply lower coincidence. Use this when your project specifies a diversity factor.
Conversions used (optional)
  • kW = kVA × PF
  • kVA = kW ÷ PF
  • 1-phase current: I(A) = kVA×1000 ÷ V
  • 3-phase current: I(A) = kVA×1000 ÷ (√3 × V)
Currents are estimates at the entered voltage and phase. Always validate against local rules, conductor temperature ratings, and protective settings.

How to Use This Calculator

  1. Select an input unit (kW, kVA, or current).
  2. Enter PF, voltage, and phase for conversions.
  3. Choose Use load list to add multiple items, or enter one connected value.
  4. Select a diversity method: percentage or factor.
  5. Optionally apply a usage factor and growth allowance.
  6. Click Calculate to show results above the form.
  7. Use the CSV/PDF buttons in the results panel to download a report.

Technical Notes and Planning Guidance

1) Why after diversity matters on site

Connected load is the sum of installed nameplate values, but equipment rarely runs together. After diversity demand (maximum demand) supports practical feeder sizing, panel allocation, and transformer selection. Many projects also carry 10–25% spare capacity on the diversified figure for operational flexibility.

2) Typical diversity ranges used in projects

Common starting points include lighting and small power at 70–90%, socket outlets at 60–80%, and cooking equipment at 50–70%. Lifts, fire pumps, and life-safety loads are often treated near 100% because they must be available on demand. Mixed commercial areas frequently land around 80–90% when occupancy is predictable.

3) Percent versus factor selection

If your schedule states “diversity 80%,” the tool multiplies connected kW by 0.80. If it states “diversity factor 1.25,” the tool divides connected kW by 1.25. Use the format written in your tender documents to avoid double-reducing demand.

4) How kW, kVA, and current relate

Many procurement checks are in kVA, while installation checks often need current. The calculator converts kW↔kVA using power factor, then estimates current using voltage and phase. For example, 50 kVA at 400 V three-phase is about 72 A, while 50 kVA at 230 V single-phase is about 217 A.

5) Load list improves traceability

The load list mode separates HVAC, lighting, sockets, pumps, and special systems. Itemized inputs make reviews faster and reduce disputes during commissioning. Exports help keep assumptions visible in RFIs, progress meetings, and handover records.

6) Usage factor and growth allowance

Some teams apply a usage factor when duty cycles are known to be higher than standard assumptions. Growth allowance adds headroom for tenant changes or future equipment. A planning range of 5–15% growth on diversified demand is common early in design, then refined at detailed stage.

7) Worked example with realistic numbers

A floor with 18 kW lighting/small power, 22 kW HVAC, and 12 kW critical loads can be diversified to 46.2 kW using 80%, 90%, and 100% respectively (14.4 + 19.8 + 12.0). With PF 0.90, that equals about 51.3 kVA for feeder checks and preliminary breaker selection.

8) Good practice before finalizing sizes

Treat the output as a design estimate, then validate with duty cycles, simultaneous operation, and code requirements. Also review starting currents, voltage drop, and harmonics for sensitive equipment. Record your assumptions so the design remains auditable during changes and future expansions.

FAQs

1) What is “after diversity demand” in simple terms?

It is the realistic maximum demand after acknowledging that not all connected loads operate simultaneously. It helps size feeders, panels, and transformers without overestimating capacity.

2) Should I use diversity percentage or diversity factor?

Use whatever your specification states. A percentage multiplies connected kW, while a factor divides connected kW. Both reduce demand, but they are expressed differently.

3) Why does the calculator ask for power factor?

Power factor converts between kW and kVA. kVA is commonly used for transformer and generator checks, while kW is used for energy and demand planning.

4) Are the current results suitable for breaker selection?

They are an estimate at the entered voltage and phase. Final breaker selection should consider code rules, ambient temperature, conductor ratings, starting currents, and coordination studies.

5) How do I handle motors and starting currents?

Use this tool for steady-state demand planning, then separately check motor starting, inrush, and voltage dip. Large motors may require dedicated feeders or soft-start arrangements.

6) What growth allowance is common in building projects?

Many teams carry 5–15% growth on diversified demand, depending on tenancy uncertainty and client preference. Higher allowances may be used for shell-and-core or expansion-ready facilities.

7) Can I export what I entered for project records?

Yes. After calculating, use the download buttons to export CSV or PDF. The export includes key inputs, totals, and the optional load list for traceable reporting.

Related Calculators

Spare capacity calculatorDisplacement PF calculatorTrue PF calculatorPF penalty calculatorPF improvement calculatorPF target calculatorFeeder voltage drop calculatorBranch voltage drop calculatorMotor voltage drop calculatorDrop limit calculator

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.