Calculator inputs
Use nominal values for quick site sizing. Verify with manufacturer data.
Example data
Typical use: powering tools, lighting, and temporary controls.
| Scenario | Bank | Input | DoD / Eff / Derate | Discharge C-rate | Runtime |
|---|---|---|---|---|---|
| Site lighting string | 24V, 200Ah (2S/1P of 12V 200Ah) | 500 W (power) | 80% / 90% / 100% | ~0.104 C | ~13:49 |
| Mobile tool charger rack | 48V, 300Ah (4S/1P of 12V 300Ah) | 90 A (current) | 70% / 88% / 95% | 0.300 C | ~02:10 |
| Temporary controls + radio repeater | 12V, 400Ah (1S/2P of 12V 200Ah) | 15 A (current) | 85% / 92% / 100% | 0.038 C | ~20:52 |
Numbers are illustrative; actual runtime depends on battery discharge curves and load dynamics.
Formula used
The calculator applies standard C-rate and runtime relationships.
- Bank capacity:
Ah_bank = Ah_single × Parallel - Bank voltage:
V_bank = V_single × Series - C-rate:
C = I / Ah_bank(charge or discharge) - Current from power:
I ≈ P / V_bank(nominal estimate) - Effective usable capacity:
Ah_eff = Ah_bank × DoD × Eff × Derate - Runtime:
t (hours) = Ah_eff / I - Target current:
I_target = C_target × Ah_bank
How to use this calculator
A practical workflow for construction site planning.
- Enter your battery unit nominal voltage and capacity.
- Set series and parallel counts for the planned bank.
- Select whether your load is known by current or power.
- Fill DoD, efficiency, and temperature derating for the site.
- Press Calculate and review C-rates and runtime.
- Use Download CSV or Download PDF for documentation.