Smart box fill calculator for electricians and engineers with live allowances by gauge device yokes grounds and clamps. Choose a standard or custom box volume watch capacity update with clear pass or fail status plus tips examples CSV and PDF export for documentation Works for common sizes supports formulas and how to use guidance
| Gauge (AWG) | Insulated conductors (qty) | Volume each (cu in) | Row volume |
|---|
| Component | Count | Factor | Volume |
|---|
This tool applies the volume allowance method from NEC 314.16(B). Total required volume is the sum of:
Required Volume = Σ(conductors × allowance_by_gauge) + (grounds ? 1 × allowance_by_ground_gauge : 0) + (clamps × allowance_by_largest_gauge) + (devices × 2 × allowance_by_device_gauge)
Notes: Pigtails that do not leave the box are not counted. External cable connectors do not count as clamps inside the box. Always confirm with the edition of the code enforced locally.
| Scenario | Gauge | Cond. | Grounds | Yokes | Clamps | Box Volume (cu in) | Req. Volume | Margin (cu in) | Status |
|---|
1) Do neutrals and travelers count?
Yes. All insulated conductors that enter or leave the box count once by their gauge, including neutrals, travelers, and switched legs.
2) Do pigtails count?
Pigtails that originate and terminate within the same box are not counted. If a pigtail leaves the box, count it like any other conductor.
3) How do devices on a yoke count?
Each yoke (switch or receptacle strap) counts as two conductor allowances of the largest conductor connected to that device.
4) What about equipment grounding conductors?
All grounds together count as a single allowance of the largest grounding conductor present in the box.
5) Do external connectors or locknuts count as clamps?
No. Only clamps that are integral to the box interior count toward volume.
6) Multiple gauges in one box?
Yes. Count each insulated conductor using its own gauge allowance. For devices and clamps, use the largest relevant gauge as specified.
7) Can I use metric units?
This tool calculates in cubic inches per NEC tables. Convert metric volumes to cubic inches before entry (1 cubic inch ≈ 16.387 cm³).
| AWG | cu in per conductor |
|---|
Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.