Breaker Sizing Calculator

Calculate breaker size from demand, phase, and power. Apply allowances for continuous loads and motors. Export results to files, document selections, and share easily.

Construction Electrical

Inputs

Fill in your system details. Use advanced factors when needed.
Tip: Keep factor values close to verified design assumptions.
Affects current calculation method.
Examples: 230, 400, 415, 480.
Use measured PF when available.
Accounts for conversion losses.
Planning multiplier for diversity or peaks.
Lower value increases required current.
Common values: 5–20%.
Typical DOL: 5–7× running current.
Useful for reports and handover.
Loads
Enter up to three general loads and two motor loads.
kW inputs
Often +25% for continuous duty.
Used only when allowance is enabled.

Example Data Table

Sample scenario for a small distribution board with mixed loads.
Phase Voltage (V) Total Load (kW) PF Eff Demand Derating Margin Design Current (A) Standard Rating (A)
Three-phase 400 25.50 0.90 0.95 1.00 1.00 10% ≈ 46.58 50
Single-phase 230 7.20 0.85 0.92 1.10 0.90 15% ≈ 49.28 50
Values are illustrative; verify assumptions for your project.

Formula Used

Core running current is computed from total real power, voltage, power factor, and efficiency.
Single-phase current
I = (P × 1000) / (V × PF × η)
P in kW, V in volts, PF is unitless, η is efficiency.
Three-phase current
I = (P × 1000) / (√3 × V × PF × η)
Line-to-line voltage is used for three-phase systems.
Design current applies planning and protection multipliers:
  • Demand factor: Idemand = Irun × demand
  • Derating: Iderated = Idemand / derating
  • Continuous allowance: multiply by (1 + continuous%/100)
  • Safety margin: multiply by (1 + margin%/100)
  • Standard rating: choose the next higher common breaker rating

How to Use This Calculator

  1. Choose system phase and enter your line voltage.
  2. Enter loads in kW. Use general and motor fields as needed.
  3. Set PF and efficiency from datasheets or measurements.
  4. Apply factors like demand, derating, continuous allowance, and margin.
  5. Click calculate to see design current and breaker rating.
  6. Download CSV or PDF for records and approvals.
Reminder: This is a sizing aid. Always confirm with local codes, cable ampacity tables, and equipment manufacturer guidance.

Load inventory and diversity

Breaker selection starts with a clean load list. Split lighting, receptacles, HVAC auxiliaries, and pumps into separate kW entries so you can review what is actually simultaneous. Many building panels operate below nameplate because not every circuit peaks together; a demand factor of 0.80–1.10 is commonly used for planning when measured data is not available. For construction temporary estimates keep a separate contingency line but do not double-count future circuits.

Power quality assumptions

Current rises when power factor or efficiency drops. A typical mixed commercial panel may see PF near 0.85–0.95, while modern variable-speed drives can change PF and harmonic content. Use equipment documentation or site measurements when possible, and treat unusually low PF as a signal to verify correction equipment and conductor sizing. Efficiency for small motors and fans may range from 0.88 to 0.96, and the same load will pull more amps when η is lower.

Continuous duty allowance

Loads expected to run for extended periods should be treated conservatively. Applying a continuous allowance of 25% helps reduce nuisance trips and limits thermal stress on terminals, busbars, and insulation. If your project defines a different rule, enter the percent that matches your specification and keep it consistent across submittals. For panelboards serving heating or process equipment, continuous operation is more likely than for office plug loads.

Derating and installation conditions

Real installations rarely match ideal catalog conditions. High ambient temperature, grouped cables, restrictive enclosures, or limited ventilation can reduce usable ampacity. A derating factor of 0.80–0.95 is often used to model harsh environments. When derating is applied, this calculator increases the required design current to maintain protection headroom.

Motor starting and trip curve choice

Motors can draw 5–7× running current at start, depending on the starting method and inertia. The calculator estimates inrush and suggests a trip curve category so the breaker is less likely to open during normal starts. Always confirm coordination with upstream protection, manufacturer guidance, and short-circuit studies for final approval.

FAQs

Should I size the breaker from kW or from measured amps?

Use measured running current when you have reliable site data. When planning, kW is acceptable if voltage, power factor, and efficiency are realistic. Recheck the result after equipment procurement and commissioning measurements.

What demand factor should I use for a mixed-use panel?

If you lack monitoring data, start near 1.00 for conservative design. For diversified loads with intermittent usage, many teams use 0.80–0.95, then validate with the owner’s load schedule and expected operating profile.

Why does derating increase the required breaker size?

Derating represents reduced heat dissipation or conductor capacity. By dividing by the derating factor, the calculator raises design current so the protective device is less likely to run hot or trip under sustained load.

How do I handle continuous loads correctly?

Enable the continuous allowance and enter the required percent. A common value is 25% for sustained operation. Apply the same rule consistently across similar panels, and confirm your local standard and project specifications.

Does the motor starting multiplier replace a coordination study?

No. It is a quick check to reduce nuisance trips during normal starts. Final selection should consider upstream devices, available fault current, cable protection, and manufacturer trip curves, typically confirmed in a coordination and short-circuit study.

Which standard breaker rating list does this tool use?

It uses a common progression of ratings (6A up to 3200A) and selects the next higher value above the design current. If your supplier uses different steps, update the list in the file to match your catalog.

Related Calculators

Paver Sand Bedding Calculator (depth-based)Paver Edge Restraint Length & Cost CalculatorPaver Sealer Quantity & Cost CalculatorExcavation Hauling Loads Calculator (truck loads)Soil Disposal Fee CalculatorSite Leveling Cost CalculatorCompaction Passes Time & Cost CalculatorPlate Compactor Rental Cost CalculatorGravel Volume Calculator (yards/tons)Gravel Weight Calculator (by material type)

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.