Plan branch circuits with clear load totals. Compare demand and continuous effects. Suggest breaker and wire size. Export results for quick field reviews instantly.
Estimate circuit demand from connected loads and diversity. Size protective devices and conductors confidently. Check voltage drop quickly for safer construction planning decisions today onsite.
| Scenario | Voltage | Connected (W) | Demand Factor | Continuous % | Approx Current (A) |
|---|---|---|---|---|---|
| Small office lighting + outlets | 230 | 2,800 | 0.90 | 60 | ~14 |
| Workshop tools mixed duty | 230 | 5,500 | 0.80 | 40 | ~26 |
| Three-phase small motor group | 400 | 12,000 | 0.85 | 50 | ~22 |
In construction, branch circuits are often revised late, when finishes and equipment lists change. A structured load estimate reduces nuisance trips, overheating, and rework. This calculator totals connected watts, applies realistic diversity, and converts the result into design current for quick sizing decisions.
Connected load is the sum of every listed device (qty × watts) plus allowances. Demand factor recognizes that not all loads run simultaneously. For example, 5,500 W of tools at a 0.80 demand factor becomes 4,400 W equivalent before other adjustments.
Many standards treat continuous loads as those expected to run for extended periods. This tool applies a 125% multiplier to the continuous portion only. If a circuit has 4,000 VA after demand and 60% is continuous, the uplift adds 0.25 × 2,400 = 600 VA, producing 4,600 VA before margin.
For AC, current is driven by apparent power (VA). Loads with PF below 1.0 draw more current for the same watts. A 2,800 W lighting circuit at PF 0.95 equals about 2,947 VA. At 230 V single-phase, that is roughly 12.8 A before demand and continuous effects.
Single-phase current uses I = VA / V. Three-phase current uses I = VA / (√3 × V). With 12,000 VA on a 400 V three-phase system, current is about 17.3 A. These distinctions help prevent undersizing when a project mixes panel types.
Long runs can cause dimming, motor stress, and control faults. Many teams target 3% for branch circuits. The calculator estimates voltage drop using circular-mil method and one-way length. If drop exceeds the target, the suggested conductor size steps up until it meets the limit.
After the design current is calculated, the tool recommends the next common breaker size. Adding a modest margin (often 5–15%) can accommodate measurement uncertainty, minor additions, and temperature effects. Always confirm local requirements for derating, bundling, and termination ratings.
Field coordination improves when calculations are traceable. Use the itemized table to show assumptions, then export CSV or PDF for submittals, RFIs, or punch-list closeout. Clear records help electricians, engineers, and inspectors align on what the circuit was designed to serve.
Use 1.00 for worst-case simultaneous use. Choose lower values for diversified loads, like general receptacles or mixed tools. If unsure, start near 0.90 and adjust based on real operating patterns.
Continuous loads are those expected to run for long durations, such as lighting, signage, or ventilation. Enter the estimated percentage; the tool applies a 125% factor to that portion only.
For AC circuits, current depends on apparent power (VA), not just watts. A lower PF increases VA for the same wattage, which raises calculated current and may require a larger breaker and conductor.
Enter the line-to-line system voltage used by your equipment and panel, such as 400 V or 480 V. The tool uses √3 in the current equation to convert VA into line current.
A 3% target is commonly used for branch circuits, while longer feeders may allow 5% overall when combined. Choose a stricter target for sensitive electronics, lighting quality, or motor starting performance.
Treat it as a planning estimate. Real installations must consider insulation temperature rating, ambient temperature, conduit fill, grouping, termination limits, and local code tables. Verify final selection with your project’s governing standard.
Breakers come in standard sizes, and continuous loads often require extra capacity. The tool also allows an engineering margin. The recommendation is the next standard size above the calculated design current.
Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.