Conduit Size Calculator

Plan wiring runs with confidence for code-aligned results every job site today. Enter conductor quantities, sizes, and insulation; get trade size, fill, spare space.

Auto uses conductor count to choose a common limit.
Used only when manual override is selected.
Keeps extra free space beyond code fill limits.

Conductors / Cables

Qty Size Insulation Custom area (in²) Help
THHN base area:
THHN base area:
THHN base area:
THHN base area:
THHN base area:
THHN base area:
Reset

Formula Used

This calculator estimates conduit trade size using an area-based fill check. First, it totals conductor cross-sectional areas, then applies a maximum fill fraction.

  • A_total = Σ (qty × A_conductor)
  • F = 0.53 (1), 0.31 (2), 0.40 (3+) conductors (or manual override)
  • F_eff = F × (1 − reserve%)
  • A_required = A_total ÷ F_eff
  • Select the smallest conduit where A_conduit ≥ A_required

Conductor and conduit areas are common NEC-style reference values; always validate against the exact products and the governing code edition for your project.

How to Use This Calculator

  1. Select a conduit type that matches your installation.
  2. Enter each conductor line: quantity, size, and insulation type.
  3. Keep fill limit on Auto, or choose Manual for a specific percentage.
  4. Optionally add a reserve percent to keep space for future work.
  5. Press Submit to see the recommended trade size and fill details.

Example Data Table

Example Conduit Type Conductors Total Area (in²) Fill Limit Recommended Trade Size
Lighting circuit EMT 6 × 12 AWG THHN 0.0798 40% 1/2"
Feeder pull RMC 3 × 4 AWG XHHW-2 0.2720 40% 3/4"
Single cable PVC Sch 40 1 × Custom (0.3000 in²) 0.3000 53% 1"

Professional Article

Why conduit sizing matters

Conduit size is more than a diameter choice; it affects safety, workmanship, inspection outcomes, and future maintainability. When a raceway is overfilled, conductors can be damaged during pulling, insulation can abrade at bends, and heat dissipation may worsen. Oversizing can also be costly and difficult to coordinate with supports and penetrations. A balanced approach starts with accurate fill calculations, then applies practical judgment for pull length, bend count, and expansion needs.

How the calculation works

The core method is area-based: each conductor or cable has a published cross-sectional area. The calculator sums these areas and divides by an allowable fill fraction to estimate the minimum conduit internal area required. Common limits are 53% for a single conductor, 31% for two conductors, and 40% for three or more conductors. You can also apply a reserve percentage to keep extra free space for future circuits or easier pulling.

Material choice and constructability

Different conduit materials offer different internal areas and installation behavior. EMT is lightweight and fast to install for interior work, while rigid options can suit exposed or industrial environments. PVC is common where corrosion resistance is important. Even with the same trade size, internal area can vary by conduit type, so selecting the correct series is essential before ordering.

Example data walk-through

Suppose you are routing six conductors of 12 AWG with standard insulation in EMT. Using typical reference areas, 12 AWG is about 0.0133 in² each, so the total is 6 × 0.0133 = 0.0798 in². With three or more conductors, the fill limit is 40%, so the required conduit area is 0.0798 ÷ 0.40 = 0.1995 in². A 1/2" EMT raceway (about 0.304 in² internal area) meets the requirement with margin.

Quality checks before installation

After a size is selected, review the full run: count bends, measure pull length, and confirm fitting types. For long runs or tight bends, stepping up one trade size can significantly reduce pull tension and labor. Keep conductors organized, use approved lubricant when needed, and protect edges at entries to prevent insulation damage.

Field documentation

Capture the conduit type, trade size, conductor list, and the calculated fill used in your submittals or as-built notes. Clear documentation helps with inspections and simplifies future modifications.

FAQs

1) What does “trade size” mean?

Trade size is the nominal conduit designation used on drawings and fittings. It does not equal the exact internal diameter, so internal area tables are used for accurate fill checks.

2) Why is the fill limit lower for two conductors?

With two conductors, the arrangement leaves more unusable void space and increases pulling friction. A lower limit reduces crowding and helps prevent damage during installation.

3) When should I use the manual fill override?

Use manual override when a project specification, authority requirement, or engineering decision sets a different fill percentage than the common default values used by the calculator.

4) What is reserve capacity used for?

Reserve capacity intentionally leaves additional empty area beyond the chosen fill limit. It supports future circuit additions and can make pulling easier, especially on long or complex runs.

5) Can I size conduit for a cable assembly?

Yes. Select “Custom” insulation and enter the cable’s published cross‑sectional area. Use manufacturer data for the most reliable result.

6) Does conduit size affect conductor heating?

Conduit fill is not a full thermal model, but tight packing can reduce air space and make pulling harder. Always follow the governing code and engineering requirements for ampacity and derating.

7) Should I choose the smallest conduit that passes?

Not always. For many bends, long pulls, or high labor risk, upsizing can improve workmanship. Use the calculated minimum as a baseline, then apply practical installation judgment.

Right-sized conduit keeps pulls smooth, safe, and compliant always.

Related Calculators

After diversity calculatorSpare capacity calculatorDisplacement PF calculatorTrue PF calculatorPF penalty calculatorPF improvement calculatorPF target calculatorBranch voltage drop calculatorMotor voltage drop calculatorDrop limit calculator

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.