Plan loops to protect valves and joints. Switch units, edit properties, and save project inputs. Get clear results instantly, then download CSV or PDF.
1) Thermal expansion of the straight run: ΔL = α · L0 · ΔT
2) Elastic stress sizing for a simple U-shaped expansion loop (preliminary sizing): Ll = √( (3 · E · D · ΔL) / (2 · S) ) where E is modulus of elasticity, D is pipe OD, and S is allowable stress.
The calculator also shows an optional quick empirical estimate used in some field checks: L ≈ 6 · √(D · ΔL) (with inches for D and ΔL).
| Scenario | Run length | Pipe OD | ΔT | Method | Recommended leg |
|---|---|---|---|---|---|
| Hot water line | 30 m | 60.3 mm | 60 °C | Elastic | ≈ 800 mm |
| Steam header | 50 m | 114.3 mm | 150 °C | Elastic | ≈ 2,100 mm |
| Chilled water | 40 m | 88.9 mm | 35 °C | Elastic | ≈ 1,000 mm |
Example values are illustrative; use project-specific properties and stresses.