Expansion tank sizing in closed-loop construction systems
An expansion tank protects a closed-loop heating or cooling system from excessive pressure caused by thermal expansion. As the fluid warms, the system’s effective volume increases. In a sealed network, that expanded volume must be absorbed. A diaphragm or bladder tank provides a compressible air cushion that accepts the expansion while keeping pressure below the relief valve setting.
This calculator estimates minimum tank size using practical inputs: total system fluid volume, temperature range (cold to hot), and pressure limits. For water, the expansion factor is computed from density change between the two temperatures. For glycol blends or specialty fluids, select the custom method and enter a supplier-provided expansion percentage for the same temperature range. The required acceptance volume is then adjusted by your safety factor and any extra acceptance allowance you include.
Tank sizing is based on ideal gas compression of the air side. The tool converts gauge pressures to absolute pressures by adding atmospheric pressure; entering site elevation refines that estimate for high-altitude work. The acceptance fraction between fill pressure and maximum operating pressure determines how much of the tank’s total volume is usable for acceptance. If you do not enter a maximum operating pressure, the calculator conservatively uses 90% of the relief setting.
Example dataset (hydronic loop): system volume 800 L, cold fill temperature 10°C, hot operating temperature 90°C. Set fill pressure to 150 kPa at the tank connection and set precharge to 150 kPa (verified with the tank isolated and drained). Set the relief valve to 300 kPa and leave maximum operating pressure blank. Add a 10% safety factor and set extra acceptance volume to 0. This case commonly returns a minimum tank size near 100 L, so a typical selection is a 100 L standard tank.
When choosing a product, remember that standard tank sizes are nominal. The acceptance available at your pressures may be lower than the total volume, so always confirm the acceptance rating and maximum temperature. If the project may expand later, consider a modest margin beyond the minimum result.
In practice, confirm the selected tank’s acceptance rating at your specific pressures and temperatures using the manufacturer’s curves. Install the tank at the correct point in the system, typically at the suction side of the circulating pump near the air separator, and include isolation and drain provisions for service. Verify relief device sizing and settings meet project specifications and local codes. Use this tool for preliminary design checks, documentation support, and commissioning verification.