Manifold Sizing Calculator

Design cleaner manifolds that feed every garden zone. Pick pipe sizes using simple inputs fast. See losses, velocities, and recommendations right after submit instantly.

Input

Choose units before entering values.
Count valves/outlets served by this header.
If you never overlap zones, enter 1.
gpm per zone at design pressure.
ft of header pipe only.
Adds length for tees, elbows, adapters (e.g., 0.25 = +25%).
Typical: PVC 150, PE 140, steel 120.
ft/s limit to reduce noise and water hammer.
psi at the manifold inlet.
psi target after manifold losses.
Used for notes and recommended phrasing.
Tip: If results are tight, reduce simultaneous zones or increase header size.

Example data table

Scenario Total zones Simultaneous zones Flow per zone Header length Velocity limit Suggested header size
Small drip garden 6 1 2.0 gpm 5 ft 5.0 ft/s 3/4"
Mixed beds and lawn 10 2 5.0 gpm 8 ft 5.0 ft/s 1-1/4"
High flow turf 12 3 8.0 gpm 10 ft 5.0 ft/s 2"
Examples are illustrative; your pipe IDs and layout may differ.

Formula used

1) Total design flow
Qtotal = zonessimul × Qzone
2) Velocity check
v = Q / A, where A = π(d/2)²
We select the smallest header meeting your velocity limit.
3) Hazen–Williams friction loss
hf = 4.52 × Q1.85 / (C1.85 × d4.87) × (L/100)
Q in gpm, d in inches, L in feet, hf in feet of head.
Pressure drop ≈ hf / 2.31 (psi). Metric values convert automatically.

How to use this calculator

  1. Select units and enter total zones on the header.
  2. Enter how many zones can run simultaneously.
  3. Provide typical flow per zone at design pressure.
  4. Add manifold length and a fitting allowance factor.
  5. Set a velocity limit to reduce hammer and noise.
  6. Enter available supply pressure and minimum required pressure.
  7. Press Calculate to see size, losses, and downloads.

Design flow and scheduling

Manifold sizing starts with demand. Total design flow equals the number of zones that can run together multiplied by typical zone flow. Overlapping zones increases header flow, velocity, and loss. When supply is limited, stagger irrigation programs or split the system into two manifolds. This calculator highlights the combined flow so you can compare layouts before buying pipe and valves.

Header length and fitting impact

Straight header length rarely tells the full story. Tees, elbows, unions, and adapters add equivalent length and increase friction. A modest allowance helps you plan for real installations without modeling every fitting. Keep runs short, avoid tight turns, and place the manifold close to the source line. Reducing fittings can save more pressure than upsizing one nominal pipe step.

Velocity targets for reliable operation

High velocity can create noise, erosion at fittings, and water hammer when valves close. Many irrigation designers aim for moderate velocities in headers to protect components and maintain stable flow. Use the velocity limit to set your preference, then select the smallest header that stays under it. If you must exceed the limit, consider pressure regulation, slower‑closing valves, or a larger header diameter.

Friction loss and pressure margin

The calculator estimates friction using the Hazen–Williams method and your chosen roughness factor. New smooth plastic typically has a higher C value than older, scaled, or metallic pipe. Loss rises steeply with flow, so small increases in simultaneous zones can reduce pressure at valves. Compare the estimated pressure after the manifold against the minimum required pressure to maintain uniform sprinkler or drip performance.

Field checks and practical recommendations

After selecting a header size, verify pipe specifications, valve port sizes, and connection types. Confirm that the supply line feeding the manifold is not undersized, because upstream loss will compound. Install a flush cap or drain for maintenance, and label valves for troubleshooting. If results show low remaining pressure, prioritize reducing overlap, shortening runs, or splitting the manifold into two sections.

FAQs

Q1: What does “simultaneous zones” mean?

It is the maximum number of zones that can run at the same time. The header must carry their combined flow, so higher overlap usually requires a larger manifold and increases friction loss.

Q2: Which pipe roughness value should I use?

Use a Hazen–Williams C value that matches your pipe condition. Smooth new plastic is often around 150, while older or rougher pipe is lower. If unsure, choose a conservative lower value.

Q3: Why does the calculator add a fitting allowance?

Fittings act like extra pipe length. The allowance approximates added loss from tees, elbows, and adapters without measuring each one. Increase it for complex manifolds and decrease it for very simple layouts.

Q4: Is the recommended valve size the same as the manifold size?

Not always. Valve sizing is usually tied to zone flow and the connected lateral, while the manifold header is sized for combined flow. Use the valve note as a starting point and confirm with manufacturer ratings.

Q5: What if the pressure check fails?

Reduce overlapping zones, shorten the manifold, use fewer fittings, increase header diameter, or split the system into multiple manifolds. Also verify upstream supply line sizing and any filters or regulators that may add loss.

Q6: How accurate are the pipe diameters in the table?

The inside diameters are typical values used for sizing guidance. Actual IDs vary by pipe class, schedule, and brand. For final design, confirm the manufacturer’s dimensions and rerun the calculation if they differ.

Related Calculators

Total dynamic head calculatorBooster pump calculatorExpansion tank calculatorHot water recirc calculatorBackflow preventer calculatorService line sizing calculatorBalancing valve calculatorFaucet flow calculatorToilet flush volume calculatorUrinal flush calculator

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.