Fire Alarm Device Calculator

Plan detectors, call points, and horns with confidence. Adjust spacing, floors, and occupancy for compliance. Export results, compare scenarios, and document design decisions quickly.

Project Inputs

Choose units for inputs and displayed labels.
Used to estimate floor-by-floor distribution.
If filled, overrides floor area × floors.
Units: m2 per floor.
Higher ceilings can reduce effective coverage.
Use lower values for partitions, beams, shelving.
Units: m · Square-grid approximation.
Units: m · Adjust per risk and room type.
/ %
Percentages are normalized if they don’t sum to 100.
Used to estimate manual call points along routes.
Devices spaced at approx 2× travel distance along egress.
Adds at least one call point per exit.
Area coverage approximation for horns/strobes.
Units: dB. Used for the simplified audibility check.
Typical target: 10–15 dB above ambient.
Units: dB. Use manufacturer datasheet values.
Used for SPL drop calculation.
Rule-of-thumb planning capacity.
Used for rough panel count planning.
Units: mA (alarm condition).
Units: mA (alarm condition).
% of notification appliances treated as horns.
% additional capacity for future changes.
Hours (battery standby planning).
Minutes (battery alarm planning).
Units: mA per panel (standby).
Units: mA per panel (alarm).
Reset
Notes: This calculator is for planning and comparisons. Always validate with applicable codes, authority requirements, and manufacturer data before final design and approvals.

Example Data Table

Scenario Floors Floor Area Smoke Spacing Heat Spacing Egress Length Exits Output (Total Devices)
Office block 3 1,200 m2 9 m 10.5 m 200 m 4
Warehouse 1 2,500 m2 10 m 12 m 140 m 2 Depends on settings
Residential mid-rise 8 900 m2 8 m 10 m 260 m 6 Depends on settings
Tip: Enter the “Office block” row values above to reproduce a comparable result.

Formula Used

  • Total area = Floors × Floor area (unless total area is provided).
  • Effective coverage factor = Obstruction factor × Height derate.
  • Detector coverage (approx.) = Spacing² × Effective coverage factor.
  • Detector count = ceil(Assigned area ÷ Coverage per detector).
  • Call points (planning) = ceil(Egress length ÷ (2× travel distance)) + Exits.
  • Notification appliances (planning) = ceil(Total area ÷ (Spacing² × 0.85)).
  • Audibility (simplified) Predicted SPL = SPL@1m − 20·log10(distance).
  • Loops (rule-of-thumb) = ceil(Initiating devices ÷ Devices per loop).
  • Panels (rule-of-thumb) = ceil(All devices ÷ Devices per panel).
  • Alarm current = (Horns×mA) + (Strobes×mA), then add margin.
  • Battery (simplified) = (Standby Ah + Alarm Ah) × 1.25 reserve.

How to Use This Calculator

  1. Select your unit system, then enter floors and area.
  2. Set ceiling height and obstruction factor for realistic coverage.
  3. Adjust smoke/heat spacing and the coverage mix for your risk profile.
  4. Enter egress length, travel distance, and exit count to estimate call points.
  5. Set notification spacing and audibility inputs to check sound assumptions.
  6. Review the results summary above the form after calculating.
  7. Export CSV/PDF to document scenarios and share with the team.

Fire Alarm Device Planning Notes

1) Define the protected footprint

Start with verified floor count and total area. For multi-storey projects, distribute devices by floor and confirm special rooms, shafts, and atriums. This tool uses total area to estimate baseline counts, then adjusts coverage using spacing and a practical obstruction factor.

2) Detector coverage assumptions

Detector quantity is driven by effective coverage (spacing squared). A 9 m smoke spacing implies about 81 m2 before derating. If obstructions and high ceilings reduce effectiveness to 0.85, coverage becomes 68.9 m2, increasing device count by roughly 17%. Use smoke/heat percentage to reflect real hazard zoning.

3) Manual call points along egress

Manual call points are estimated from egress length and maximum travel distance. With 200 m of travel path and a 30 m travel target, the run spacing becomes 60 m, producing about 4 devices, plus exits. Always place devices at exits and stair doors as required by local authority.

4) Notification and audibility check

Notification appliances are planned by area coverage and spacing. Audibility is checked using a simple 20·log10(distance) drop from the device output at 1 m. For example, a 90 dB device at 10 m predicts about 70 dB. If ambient is 60 dB and margin is 15 dB, the 75 dB target requires closer spacing or higher output.

5) Loops, panels, and power budgeting

The calculator provides rule-of-thumb planning counts for addressable loops and control panels using user-set capacities. Power sizing uses horn/strobe current draws with a margin, then estimates battery capacity from standby hours and alarm minutes with a reserve factor. Replace these assumptions with manufacturer data during detailed design and commissioning.

FAQs

1) Is this output a final code-compliant design?

No. It is a planning estimate for early sizing, comparisons, and documentation. Final layouts must follow applicable codes, authority requirements, and manufacturer listings.

2) Why do counts change when I adjust obstruction factor?

Obstructions reduce effective coverage. Lower factors shrink coverage per device, so more detectors and appliances are required to protect the same area.

3) How should I choose smoke and heat percentages?

Use them to represent zoning decisions. Higher smoke share suits occupied spaces; higher heat share suits dusty, steamy, or high-nuisance areas. Normalize helps when totals are not 100%.

4) What does the audibility PASS/REVIEW mean?

It compares predicted sound level at a worst-case distance with a target above ambient. REVIEW means assumptions may not meet audibility; revise spacing, outputs, or zones.

5) Can I model strobes separately from horns?

Yes. Set horn share to control the split of appliances. Enter distinct mA values for horns and strobes to refine alarm current and battery planning.

6) How do loops and panels get calculated?

They are computed by dividing initiating devices and total devices by your capacity settings, then rounding up. Treat this as early planning, not a hardware submittal.

7) Why does imperial mode still show some results in metric?

Inputs and labels switch to ft and ft2, while internal calculations use meters for consistency. The summary area converts back for display, but coverage values remain in m2.

Related Calculators

Paver Sand Bedding Calculator (depth-based)Paver Edge Restraint Length & Cost CalculatorPaver Sealer Quantity & Cost CalculatorExcavation Hauling Loads Calculator (truck loads)Soil Disposal Fee CalculatorSite Leveling Cost CalculatorCompaction Passes Time & Cost CalculatorPlate Compactor Rental Cost CalculatorGravel Volume Calculator (yards/tons)Gravel Weight Calculator (by material type)

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.