HEPA Scrubber Count Calculator

Plan containment ventilation with confidence today everywhere. Compare ACH goals, derating, and equipment capacity fast. Download clean summaries for bids, crews, and inspections now.

Calculator

Enter space size, target ACH, and scrubber airflow to estimate count.

All calculations run locally on this page.

Choose the measurement system for space inputs.
Pick how you want to describe the space.
Enter a room count from 1 to 999.
Multiplies volume and airflow requirements.
Measured inside containment.
Use the average width if irregular.
Typical ceiling height within the space.
Useful for complex shapes or measured volume.
Enter an ACH value from 1 to 60.
Common containment targets are often 4–12 ACH.
Enter an airflow rating of at least 50.
Use the manufacturer rating at your chosen configuration.
Enter a percent from 40 to 100.
Typical derate: 70–90% depending on setup.
Enter a percent from 0 to 50.
Adds margin for uncertainty and real-world conditions.
Use small values unless you have measured data.
Reset

Reminder: Always follow project requirements, containment standards, and manufacturer guidance.

Formula used

The calculator estimates the airflow needed to reach a target number of air changes per hour. Then it divides by the effective airflow of each scrubber (after derating), and rounds up.

How to use this calculator

  1. Select your unit system and input method.
  2. Enter the space dimensions or a measured volume.
  3. Set the ACH target required by your scope or standard.
  4. Enter the scrubber airflow rating and choose a realistic derate.
  5. Add a safety factor and optional leakage allowance if needed.
  6. Press Calculate and download a CSV or PDF summary for records.

Example data table

Scenario Space Target ACH Scrubber rating Derate Safety Estimated count
Small room 12 ft × 10 ft × 8 ft 6 500 CFM 85% 10% 2
Medium work zone 20 ft × 15 ft × 9 ft 8 2000 CFM 80% 10% 2
Large bay 50 ft × 30 ft × 12 ft 6 3000 CFM 75% 15% 5
Two identical rooms 2 × (18 ft × 14 ft × 8 ft) 6 1000 CFM 80% 10% 3
Metric example 10 m × 6 m × 3 m 6 3400 m3/h 80% 10% 4

Examples are illustrative; actual requirements depend on containment performance and project scope.

ACH to airflow conversion

Air changes per hour (ACH) convert directly into required airflow. The calculator uses CFM = (Volume × ACH) ÷ 60, so a 2,400 ft3 zone at 6 ACH needs 240 CFM before margins. Doubling ACH doubles airflow demand. For multi-room repeats, the tool multiplies volume by the room count, keeping the same ACH target across identical spaces. For quick checks, confirm units and ceiling height.

Volume inputs and unit handling

Room volume drives everything, so measuring accurately matters. Dimensions mode computes L × W × H, while Volume mode lets you enter a surveyed value for irregular areas. A 20 ft × 15 ft × 9 ft space equals 2,700 ft3; at 8 ACH it needs 360 CFM baseline. Switching to metric accepts meters and cubic meters and converts internally. Include mezzanines only when air is connected.

Derating scrubber performance

Scrubber ratings rarely match field performance, so the derate input adjusts capacity for loaded filters, bends, and duct runs. For example, a 2,000 CFM unit derated to 80% provides 1,600 effective CFM. Two such units yield 3,200 effective CFM. The count is rounded up to avoid under-ventilation when conditions change during the shift. Use manufacturer curves when available.

Safety and leakage allowances

Safety and leakage allowances add practical resilience. A 10% safety factor increases required airflow by 1.10, and a 5% leakage allowance multiplies again to 1.155 overall. These margins help when doors open, seams flex, or make-up air pathways vary. If you have measured negative pressure behavior, tune leakage to match site observations. When unsure, start conservative, then verify with pressure tests.

Cleanup time estimation

The results estimate cleanup time using a mixing model. Once ACH achieved is known, time to a remaining fraction uses t = (−ln(remaining) × 60) ÷ ACH. At 10 ACH achieved, reaching 99% reduction (1% remaining) takes about 27.6 minutes. Use this as a guide, not a compliance certificate. Schedule filter changes to maintain the achieved ACH daily.

FAQs

1) How do I choose a target ACH?

Use your project specification or containment plan first. When none is stated, many teams start around 4–12 ACH, then verify performance with field checks and adjust scrubber count as needed.

2) What derate percentage should I enter?

If you run long ducting, multiple bends, or loaded filters, derate more. A practical starting point is 70–90%. Use measured airflow or manufacturer curves whenever you can.

3) Should I enable leakage allowance?

Enable it when enclosures are temporary, doors open often, or you expect make-up air variability. Start with 3–8%, then refine after observing pressure stability and smoke movement.

4) Can I calculate multiple rooms at once?

Yes. Enter the number of identical rooms and the tool multiplies the volume accordingly. If rooms differ, calculate each room separately and sum the scrubber totals.

5) Does the calculator support metric inputs?

Yes. Select Metric to enter meters and cubic meters. Scrubber airflow can be entered as m3/h or CFM, and all results are normalized internally for consistent calculations.

6) Are the reduction-time estimates guaranteed?

No. They assume well-mixed air and steady effective airflow. Use them for planning and sequencing. Real cleanup time can change with obstructions, leakage, and filter loading.

Related Calculators

Mold Moisture Source CalculatorIndoor Humidity Risk CalculatorDew Point Mold CalculatorSurface Condensation Risk CalculatorWall Cavity Moisture CalculatorBasement Dampness Index CalculatorVentilation Rate Mold CalculatorAir Exchange Need CalculatorBathroom Exhaust Sizing CalculatorKitchen Ventilation Need Calculator

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.