Radiator Sizing Calculator for Building Heating

Enter dimensions, insulation, windows, and design temperatures for heat demand. Choose radiator type and water temps to match realistic output ratings. Add safety margin.

Calculator Inputs
Responsive grid: 3 columns (large), 2 columns (medium), 1 column (mobile).
Internal calculations use metric, then convert if needed.
Used in exports and report header.
Detailed is better when you know surface areas and U-values.
Leave blank to use length × width.
Used mainly for the quick transmission estimate.
Typical: 0.3–0.7; higher for workshops.
Used to estimate exposed wall area in detailed mode.
Typical: 0.2–0.8 W/m²K.
Common: 10–20% for uncertainty and setbacks.
Common basis is ΔT 50 K (room 20°C).
Preset fills typical exponent and unit rating; you can override.
Typical: 1.25–1.35 for panel radiators.
Metric: W. Imperial: BTU/h.
Tip: For detailed mode, check U-values against your local energy code or product datasheets.
Example Data Table
Scenario Area (m²) Height (m) Indoor (°C) Outdoor (°C) ACH Design Load (W) Rated at ΔT50 (W) Units
Bedroom, average insulation 16 2.6 20 -2 0.5 1,650 2,050 2
Office, good insulation 24 2.8 21 -5 0.4 2,150 2,600 2
Workshop, leaky envelope 30 3.0 18 -5 1.2 5,100 6,400 4
Example outputs are illustrative; always validate with manufacturer performance tables.
Formula Used

1) Transmission heat loss

Detailed method uses Q = Σ(U × A × ΔT), where U is the thermal transmittance (W/m²K), A is surface area (m²), and ΔT is the indoor–outdoor temperature difference (K).

2) Ventilation and infiltration loss

Ventilation heat loss is estimated by Qvent = 0.33 × ACH × V × ΔT. Here ACH is air changes per hour, and V is room volume (m³).

3) Design load with allowances

Total heat loss is multiplied by distribution and safety factors: Qdesign = (Qtrans + Qvent) × (1 + L) × (1 + S), where L is pipe loss fraction and S is safety margin fraction.

4) Radiator output correction

Radiator output varies with mean water temperature. The correction uses CF = (ΔTactual/ΔTstandard)n, with ΔTactual = ((Ts + Tr)/2) − Troom. Required standard rating is Qrated = Qdesign/CF.

How to Use This Calculator
  1. Pick your units and enter room dimensions and ceiling height.
  2. Set indoor and outdoor design temperatures for your climate.
  3. Enter ACH for ventilation or infiltration, then add allowances.
  4. Choose quick or detailed method based on available building data.
  5. Enter supply/return water temperatures from your heating system.
  6. Use manufacturer output at the chosen standard ΔT as unit rating.
  7. Click Calculate, then export results to CSV or PDF.
Professional Article

Design conditions and comfort targets

Start with a clear indoor setpoint, commonly 20–21°C for living areas and 18°C for bedrooms. Select an outdoor design temperature from local climate data, then keep it consistent across the project. The difference between indoor and outdoor temperatures drives the heat loss and the final emitter size.

Fabric heat loss and realistic U‑values

Transmission loss is dominated by envelope area and U‑value. Typical ranges are 0.2–0.35 W/m²·K for well‑insulated walls, 1.2–2.8 W/m²·K for glazing, and 0.12–0.25 W/m²·K for roofs. Measuring wall, window, and floor areas carefully often improves accuracy more than tweaking any single assumption.

Ventilation and infiltration allowances

Fresh air is essential, but it also carries heat away. Many residential rooms fall between 0.5 and 1.0 air changes per hour, while leaky sites can exceed 1.5. Use tighter values for sealed construction and higher values for older buildings, large openings, or windy exposures.

Internal gains and practical safety factors

Heat gains from people, lighting, and equipment can offset part of the loss, yet they vary by occupancy and use. On site, designers often apply a 10–15% allowance to cover uncertainty, intermittent door opening, and uneven insulation. Smaller zones can reduce oversizing and improve control.

Converting heat load into radiator capacity

Once the design load is known, match it to an emitter that can deliver the same watts at your operating conditions. If you also track BTU/h, use 1 W = 3.412 BTU/h for quick checks. Always compare the required output against the selected radiator’s published rating and size the nearest standard model upward.

Water temperature correction and ΔT logic

Radiators are usually rated at a standard temperature difference, such as ΔT 50 K. Lower flow temperatures reduce output, especially with heat pumps. A correction factor uses CF = (ΔTactual/ΔTstandard)n, where n is often about 1.3 for panel units. This step prevents undersizing when you operate at 55/45°C or lower.

Radiator selection, placement, and clearances

Panel, column, and convector styles behave differently in real rooms. Maintain clearance for air circulation, avoid deep covers, and consider cold‑down‑draft near glazing. Mounting height, wall reflectivity, and pipe entry positions all affect perceived comfort. In tight layouts, two smaller emitters can outperform one oversized unit.

Commissioning, controls, and long‑term performance

After installation, balance the system so each radiator receives the intended flow. Pair thermostatic valves with room zoning and a sensible setpoint schedule to prevent overheating. Bleeding air, checking pump settings, and confirming return temperatures protects efficiency. Regular cleaning preserves convection and stable output over time.

FAQs

What indoor temperature should I design for?

Use comfort setpoints that match the room use: about 20–21°C for living spaces, 22°C for bathrooms, and 18°C for bedrooms. Consistency matters more than choosing a perfect number.

How do I pick U‑values if I do not have drawings?

Start with typical guidance ranges for your construction type, then refine with insulation thickness and material data. When uncertain, choose the higher U‑value to stay conservative, and document the assumption.

Should I oversize radiators for faster warm‑up?

A modest allowance, often 10–15%, helps with intermittent heating and unexpected drafts. Larger oversizing can cause short cycling and poor control, so prefer zoning and better insulation before adding big margins.

What water temperatures suit condensing boilers or heat pumps?

Condensing boilers often target lower returns, so 70/50°C may be reduced to 60/40°C or 55/45°C. Heat pumps typically run even lower. Enter your planned supply and return temperatures so the correction factor reflects reality.

Do curtains, covers, or furniture reduce radiator output?

Yes. Blocking the airflow can cut heat transfer noticeably and create cold spots. Keep a clear convection path above and below the radiator, and avoid full‑height covers unless they are specifically designed for airflow.

Can one radiator serve two rooms through an open doorway?

It can, but results depend on airflow and door habits. Temperature will usually be uneven. For predictable comfort and control, size emitters per room or use a designed transfer opening with careful balancing.

Why does the calculator include an allowance percentage?

It accounts for real‑world uncertainty: varying wind, imperfect insulation, door opening, and installation tolerances. A small allowance can prevent complaints, but it should not replace proper envelope design and airtightness.

Accurate sizing saves energy, money, and comfort long-term today.

Related Calculators

subcooling calculatorhspf calculatoroccupancy load calculatormotor efficiency calculatorkw to btu calculatorhumidifier sizing calculatorduct velocity calculatorrefrigerant charge calculatorfan curve calculatorRoom BTU calculator

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.