Solve single‑phase power using flexible input methods. Compare kW, kVA, kVAR, and current. Export results for reports and site approvals. Create tables for crews.
| Inputs | V | A | PF | kW | kVA | kVAR |
|---|---|---|---|---|---|---|
| V, I, PF | 230 | 15 | 0.90 | 3.105 | 3.450 | 1.504 |
| V, kW, PF | 120 | — | 0.85 | 2.000 | 2.353 | 1.238 |
| kW, kVAR | 230 | — | — | 5.000 | 5.831 | 3.000 |
Single‑phase circuits power lighting strings, receptacle panels, small compressors, mixers, pumps, heaters, office trailers, and hand tools. These loads can change quickly as crews move, so a fast power check helps match temporary feeders and generators to real demand.
For single‑phase, apparent power is S = V × I. A 230 V circuit at 15 A is 3.45 kVA, while the same current at 120 V is 1.80 kVA. The calculator converts these directly and keeps units consistent for planning.
Real power is P = S × PF. If PF is 0.90, the 3.45 kVA example becomes 3.105 kW. This number aligns with energy consumption and heating, so it supports fuel estimates, runtime planning, and cost tracking for temporary installations.
Reactive power is Q = √(S² − P²). For 3.45 kVA and 3.105 kW, Q ≈ 1.50 kVAR. Motors and transformers create reactive demand, increasing current without adding useful work. Understanding Q helps prevent overloaded cords and nuisance breaker trips.
Power factor is PF = P/S and relates to phase angle by PF = cos φ. The calculator can accept PF or φ and returns both. For PF = 0.85, φ ≈ 31.8°. Angle inputs are useful when commissioning reports list φ instead of PF.
Field data is rarely perfect. You might have voltage and current from a clamp meter, kW from a meter, or kW and kVAR from a panel analyzer. The tool supports several methods so you can calculate kVA, kW, kVAR, PF, and angle using what you actually know. This flexibility reduces rework when readings are incomplete.
Use kVA to estimate upstream capacity and voltage drop risk. Many crews keep continuous loading below about 80% to manage heat and starting surges. If you enter optional voltage with kW and kVAR, the calculator also estimates current for quick cable and breaker checks. Always confirm final selections against local codes and manufacturer limits.
Temporary power often requires documented calculations for approvals and audits. Exporting CSV supports spreadsheets and daily logs, while the PDF format fits site folders and submittals. Re-run the calculation when equipment changes, panels move, or new areas energize. Keeping dated exports improves troubleshooting if voltage or overheating complaints appear later.
Use measured voltage, measured current, and measured power factor when possible. If you have kW and kVAR from an analyzer, that combination is also highly reliable for computing kVA and PF.
Breakers, cables, and generators respond to current. Current is tied to kVA, not just kW, because reactive power increases RMS current even when useful work stays the same.
Low power factor usually means inductive or nonlinear loads, such as motors or certain power supplies. It increases kVA and current for the same kW, which can stress temporary wiring.
Yes. Negative kVAR indicates leading reactive power, often from capacitors or lightly loaded long cables. Positive kVAR is typically lagging and associated with inductive equipment.
They are equivalent because PF = cos φ. If you know φ, the calculator derives PF and then computes kW, kVA, and kVAR. Use whichever value you have available.
Compute kVA as √(kW² + kVAR²), then I = (kVA × 1000) / V. Enter an optional voltage in the kW and kVAR method to have the calculator do this automatically.
No. Harmonics can increase RMS current beyond the fundamental power triangle. For critical sizing, review THD, apply derating guidance, and verify with measurements during peak operation.
Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.