Three Phase Voltage Drop Guide
Three phase voltage drop matters on long feeders. It shows how much line voltage is lost before the load. Large drop can reduce motor torque. It can also heat cables and waste energy. A good estimate helps before wire is purchased.
Why It Happens
Current flows through conductor resistance and reactance. Resistance creates heat. Reactance appears because alternating current makes a magnetic field. The effect grows with current, distance, and poor power factor. Three phase systems use the square root of three in the line voltage formula.
Important Design Inputs
The calculator uses line voltage, design current, one way length, conductor size, material, temperature, power factor, and reactance. Parallel runs are also included. They reduce the effective impedance. A temperature setting adjusts resistance because hot conductors resist current more. The installation multiplier can add design allowance for crowded raceways, old conductors, or conservative planning.
How To Read Results
The voltage drop value shows the estimated lost volts. The percentage compares that loss with the source line voltage. The load voltage shows the expected voltage at equipment terminals. The pass or review message compares the result with the allowed limit. Many designers aim for a low branch circuit drop. Long feeders may need a larger conductor.
Practical Example
Assume a 480 volt motor feeder. The current is 80 amps. The one way run is 250 feet. The power factor is 0.85 lagging. A copper conductor has resistance and reactance along the run. The formula estimates line loss. If the percentage is high, try a larger conductor. You can also shorten the route, use parallel runs, or improve power factor.
When Larger Wire Helps
Larger wire lowers resistance. That reduces heat and line loss. It may improve starting voltage for motors. It can also support future load growth. The tradeoff is higher material cost and larger raceway needs.
Design Notes
This calculator is for planning and comparison. Final installations should follow local electrical code. Use the actual cable table required by your standard. Check conductor ampacity, temperature rating, terminals, conduit fill, fault current, and protection settings. Voltage drop is only one part of safe design. Always document assumptions before ordering material and future maintenance checks later.