When two or more transformers operate in parallel, discrepancies in their voltage ratings, tap settings, or internal impedance values can cause a closed-loop current to flow between their secondary windings even under no-load conditions. This phenomenon is known as circulating current.
The circulating current ($I_c$) magnitude is determined using the voltage difference between the secondary windings divided by the sum of their individual impedances:
$$I_c = \frac{|V_1 - V_2|}{Z_1 + Z_2}$$
Where $V_1$ and $V_2$ represent the secondary no-load voltages, while $Z_1$ and $Z_2$ represent the total complex impedances ($Z = \sqrt{R^2 + X^2}$) of respective transformer branches.