Estimate current, power, energy, and running cost accurately. Size circuits with demand and safety adjustments. Plan safer single phase installations with clearer electrical decisions.
This example shows a common workshop load scenario using the current mode. Values are rounded for readability.
| Item | Example Value |
|---|---|
| Calculation Mode | From current |
| Supply Voltage | 230 V |
| Input Current | 12 A |
| Power Factor | 0.90 |
| Efficiency | 95% |
| Demand Factor | 0.85 |
| Load Factor | 0.70 |
| Safety Margin | 20% |
| Hours Per Day | 8 |
| Days Per Month | 30 |
| Rate Per kWh | 0.15 |
| Approximate Design Current | 12.88 A |
| Approximate Monthly Energy | 373.39 kWh |
| Approximate Monthly Cost | 56.01 |
Apparent Power: S = V × I
Active Power: P = V × I × PF
Current From Power: I = P / (V × PF)
Current From Apparent Power: I = S / V
Connected Load: Connected Load = Base Load × Quantity
Demand Load: Demand Load = Connected Load × Demand Factor
Input Power: Input Power = Demand Active Power / Efficiency
Design Load: Design Load = Input Power × (1 + Safety Margin)
Average Operating Power: Average Power = Input Power × Load Factor
Daily Energy: Daily kWh = (Average Power / 1000) × Hours Per Day
Monthly Energy: Monthly kWh = Daily kWh × Days Per Month
Monthly Cost: Monthly Cost = Monthly kWh × Rate Per kWh
This calculator assumes a single phase supply and applies the same power factor through the adjusted demand and design stages. Use project standards and local codes for final equipment selection.
It estimates current, active power, apparent power, design load, energy use, and running cost for a single phase electrical load using common planning inputs.
Power factor links active power and apparent power. A lower power factor increases current for the same useful power, affecting circuit sizing and losses.
Demand factor reduces connected load to a more realistic simultaneous load. It helps planners avoid sizing a circuit only from total nameplate values.
Efficiency accounts for input losses. If a device is less than fully efficient, the source must deliver more power than the useful output demand.
Load factor adjusts average operating power for energy and cost estimates. It does not replace demand factor, which is used earlier for diversified loading.
No. It is a planning recommendation based on calculated design current. Final breaker selection must follow code rules, conductor rating, ambient conditions, and starting current behavior.
Yes, for preliminary estimates. For motors, also consider inrush current, service factor, duty cycle, and local protection requirements before finalizing equipment.
No. It supports early sizing and budgeting. Final design should still be checked against standards, manufacturer data, and project-specific installation conditions.
Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.