AC Voltage Drop Planning Guide
Why Voltage Drop Matters
Voltage drop happens when current moves through real conductors. Every conductor has resistance. AC circuits also have reactance. These values reduce the voltage available at the load. A small drop is normal. A large drop can cause dim lights, weak motors, warm conductors, nuisance trips, and poor equipment performance.
Important Inputs
This calculator uses phase, current, source voltage, one-way distance, conductor material, conductor area, temperature, power factor, and reactance. Each input changes the final result. Longer runs increase drop. Higher current increases drop. Aluminum usually drops more voltage than copper for the same size. More parallel runs reduce effective impedance.
Single-Phase and Three-Phase Circuits
Single-phase calculations use a round-trip conductor factor of two. Three-phase calculations use the square root of three. This is why a three-phase result may look different from a single-phase result with the same current and length. The calculator treats the entered length as one-way length only.
Power Factor and Reactance
AC voltage drop is not only a resistance problem. Motor loads and transformer loads can have lagging power factor. That makes reactance more important. The calculator includes a reactance estimate and a custom reactance option. Leading power factor can reduce the reactive part of the drop.
Using the Result
The result shows volts dropped, percent drop, receiving voltage, power loss, effective impedance, and a suggested conductor size. Many designers use three percent for branch circuits and five percent for combined feeder and branch runs. These are common planning targets. They do not replace code rules. Always verify ampacity, insulation rating, terminals, ambient correction, conduit fill, grounding, and local authority requirements before installation.