Wire Size Voltage Drop Calculator

Size wires with drop, temperature, material, and phase inputs. Review losses, resistance, and ampacity checks. Export results for records and field planning today fast.

Calculator Inputs

Example Data Table

Voltage Current Length Material Phase Drop Limit Typical Use
120 V 20 A 80 ft Copper Single phase 3% Branch circuit
240 V 50 A 140 ft Copper Single phase 3% Shop feeder
480 V 100 A 250 ft Aluminum Three phase 5% Motor feeder

Formula Used

Single phase or direct current: Voltage drop = 2 × K × I × D × PF ÷ CMIL ÷ parallel runs.

Three phase: Voltage drop = 1.732 × K × I × D × PF ÷ CMIL ÷ parallel runs.

Voltage drop percent: Voltage drop percent = voltage drop ÷ system voltage × 100.

Temperature adjusted K: Kt = K20 × [1 + alpha × (temperature C − 20)].

Ampacity check: available ampacity = table ampacity × derating percent × parallel runs.

K is conductor resistance in ohm circular mils per foot. D is one way length in feet. PF is power factor.

How to Use This Calculator

Enter the system voltage and load current. Add the one way distance from source to load. Select the circuit type, conductor material, and wire size to test. Enter your allowed voltage drop limit. Add power factor for alternating current loads. Use one for direct current. Enter derating and continuous load values. Press the calculate button. The result appears above the form.

Wire Sizing Matters

Voltage drop is the voltage lost along conductors before power reaches the load. A small drop is normal. A large drop can heat wires, dim lights, slow motors, and waste energy. Good design keeps the drop within a chosen limit. Many designers use three percent for branch circuits. They often use five percent for the whole feeder and branch path.

What This Tool Checks

This calculator compares voltage, current, distance, phase, material, temperature, power factor, and parallel runs. It also checks a selected wire against a target drop limit. Then it finds the smallest listed conductor that meets the drop target and an ampacity check. The ampacity values are planning references. Local codes, insulation ratings, terminals, conduit fill, bundling, and ambient conditions can change the final answer.

Better Inputs Give Better Results

Use one way circuit length. Do not enter the round trip length. The formula adds the return path for single phase and direct current circuits. For three phase circuits, it uses the square root of three factor. Enter the real load current, not just breaker size, unless breaker loading is your design basis. For continuous loads, increase the load percentage when your code requires it.

Copper And Aluminum Choices

Copper has lower resistance than aluminum. It usually allows a smaller conductor for the same voltage drop. Aluminum is lighter and may cost less for feeders. It often needs a larger size and correct terminations. Temperature also matters. Resistance rises as conductors warm. A hotter conductor creates more drop and more losses.

Using Results In Design

Start with the recommended wire size. Review the selected wire result too. If it fails, increase conductor size, reduce length, raise voltage, add parallel runs, or lower load current. Check the calculated power loss. High loss can make a compliant design expensive to operate. Always verify the final conductor with an electrical code table and a qualified professional. This tool supports planning. It does not replace engineered approval for critical work.

Document assumptions before buying cable. Save the CSV for estimates. Save the PDF for review notes. Compare several limits when equipment is sensitive. Motors, pumps, welders, and long outdoor runs may need stricter planning margins and future maintenance records.

FAQs

What length should I enter?

Enter the one way distance from the power source to the load. Do not enter round trip length. The calculator applies the proper circuit factor.

What voltage drop limit should I use?

Many designs use three percent for branch circuits. Some feeders allow five percent total. Sensitive equipment may need a lower value.

Does this replace an electrical code table?

No. It supports planning only. Always check local code, conductor insulation, terminal temperature, conduit fill, and breaker rules before installation.

Why does aluminum need a larger wire?

Aluminum has higher resistance than copper. Higher resistance creates more voltage drop, so larger aluminum conductors are often needed.

What is power factor?

Power factor describes how efficiently alternating current does useful work. Motors and transformers often have lower power factor than heaters.

Why include temperature?

Conductor resistance rises with temperature. Higher resistance increases voltage drop and heat loss along the circuit.

What are parallel runs?

Parallel runs split current across multiple conductors. This can reduce voltage drop and increase available ampacity when installed correctly.

Why does the selected wire fail?

It may exceed the voltage drop limit or lack enough derated ampacity. Increase size, reduce length, or adjust load assumptions.

Related Calculators

Paver Sand Bedding Calculator (depth-based)Paver Edge Restraint Length & Cost CalculatorPaver Sealer Quantity & Cost CalculatorExcavation Hauling Loads Calculator (truck loads)Soil Disposal Fee CalculatorSite Leveling Cost CalculatorCompaction Passes Time & Cost CalculatorPlate Compactor Rental Cost CalculatorGravel Volume Calculator (yards/tons)Gravel Weight Calculator (by material type)

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.