Foam Concentrate Calculator

Size concentrate tanks using flexible engineering inputs fast. Handle multiple nozzles, units, and reserves easily. Get accurate results, then download CSV or PDF files.

Use devices when several discharge points operate together.
All flows are converted internally to L/min.
Typical hydrocarbon fuel foam.
Typical values are 1%, 3%, or 6%.
Often based on hazard and design standard.
Common range: 5–20% for uncertainty and losses.
Add a fixed reserve for refill delays or testing.
Enter the overall system flow in the chosen unit.
If unsure, select worst-case for storage sizing.
Device flow list
Enable devices that operate simultaneously.
Up to 6 devices
On Device name Flow (lpm)
Reset
Tip: Concentrate volume is calculated in liters. If you need gallons, export CSV and convert.

Example data table

This sample demonstrates how device flows add up to a total.

Example device Flow (L/min) Enabled
Monitor500Yes
Sprinkler zone300Yes
Handline100No
For the enabled rows, total flow = 500 + 300 = 800 L/min.

Formula used

  • Total solution flow (L/min) = sum of enabled device flows (converted to L/min).
  • Solution volume (L) = Total solution flow × Application time (min).
  • Base concentrate volume (L) = Solution volume × (Concentration ÷ 100).
  • Adjusted concentrate volume (L) = Base concentrate × (1 + Safety factor ÷ 100) + Reserve volume.
  • Suggested tank size = next standard size ≥ Adjusted concentrate volume.

How to use this calculator

  1. Select Calculation mode and your preferred flow unit.
  2. Choose a foam type preset or use Custom.
  3. Enter application time, safety factor, and any reserve volume.
  4. If using devices, enable the ones operating together and input their flows.
  5. Press Calculate. Results appear above the form.
  6. Use the buttons in the results panel to download CSV or PDF.

FAQs

1) What does “foam concentrate” mean here?

It is the stored foam liquid that mixes with water at a set percentage to create the foam solution delivered to devices.

2) Should I size using 3% or 6% for AR-AFFF?

If the hazard includes polar solvents, use 6%. If only hydrocarbons, 3% may be acceptable. When unsure, pick worst-case for storage.

3) Why add a safety factor?

Safety factor covers uncertainties such as flow variation, proportioner tolerances, hose losses, testing consumption, and operational delays during an incident.

4) What if devices do not run at the same time?

Only enable devices expected to operate simultaneously. If operations are staged, run separate scenarios and select the largest concentrate requirement.

5) Are the results suitable for code compliance?

This tool supports engineering estimation. Always confirm assumptions with the applicable standard, authority requirements, and the foam manufacturer’s data.

6) Why does the calculator suggest a “standard tank size”?

Storage tanks come in discrete sizes. Selecting the next available size above the calculated requirement helps avoid shortfalls and supports procurement.

7) Can I use gallons instead of liters?

Yes. Enter flow in gpm, export results, and convert volumes if desired. Internally, calculations use liters for consistency.

Related Calculators

Fire Load CalculatorSprinkler Flow RateHydrant Flow CalculatorStandpipe Flow CalculatorFire Water StorageTank Capacity CalculatorNozzle Discharge CalculatorHazard Classification ToolExit Capacity CalculatorSmoke Exhaust Rate

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.