UPS Battery Sizing Calculator

Design dependable backup power with detailed battery sizing. Model inverter losses, surge demand, and margins. Compare battery options, then export results for documentation easily.

Inputs

Average real power you need to back up.
Motor start or inrush peak power.
Required autonomy at the stated load.
Used for VA sizing guidance.
Typical 0.85–0.95 depending on size.
Common: 12, 24, 36, 48, 96, 192.
Typical lead-acid: 12 V, VRLA: 12 V.
Nameplate at 20-hour rate (common).
0.5–0.8 typical for longer life.
Capacity fade over years (e.g., 1.25).
Extra capacity for cold rooms or heat stress.
Uncertainty buffer for real-world operation.
Accounts for ripple and conversion losses (1.02–1.08).
Reset

Example Data

Use this sample to sanity-check your settings.

Scenario Inputs (key) Typical outcome
Small Office Router Load 60 W, Surge 80 W, 120 min, 24 V bus, 12 V 18 Ah 2S × 1P (2 batteries), ~18–25 Ah string
Home Workstation Load 350 W, Surge 600 W, 30 min, 48 V bus, 12 V 100 Ah 4S × 1P (4 batteries), ~25–40 A DC nominal
Critical Comms Rack Load 1200 W, Surge 1800 W, 30 min, 48 V bus, 12 V 100 Ah 4S × 1P (4 batteries) to 4S × 2P, by margins

Formulas Used

1) DC power from batteries
PDC = (Pload / η) × Kripple × Kmargin
η is UPS efficiency, and K factors add conservative buffers.
2) Required energy
EWh = PDC × th
th is runtime in hours (minutes ÷ 60).
3) Amp-hour capacity at DC bus
Ahbus = EWh / VDC
VDC is the UPS DC bus voltage.
4) Derating, aging, and usable depth
Ahreq = Ahbus × Kaging × Ktemp ÷ DoD
Lower DoD improves life but needs more batteries.
5) Series and parallel counts
Series = ceil(VDC / Vunit), Parallel = ceil(Ahreq / Ahunit)
Series sets voltage; parallel increases capacity (Ah).
Note: For very long runtimes or high currents, you should also apply battery discharge-rate effects (Peukert behavior) from the battery datasheet. This tool provides a conservative engineering estimate.

How to Use

  1. Enter average load and the maximum surge power.
  2. Set the required backup time in minutes.
  3. Choose the UPS DC bus voltage and battery unit voltage.
  4. Enter the battery unit amp-hour rating from its datasheet.
  5. Adjust DoD, aging, temperature, and margin factors.
  6. Press Calculate to see sizing and configuration.
  7. Download CSV or PDF for records and quoting.

Load profiling and runtime targets

Start with a measured watt profile, not nameplate labels. A 1,200 W rack often averages 700–900 W. Use the peak surge for inrush and fan start. Convert minutes to hours for energy planning. For 30 minutes at 1,200 W, load energy equals 600 Wh before any losses. If power factor is 0.9, the apparent demand is about 1,333 VA, so select UPS capacity with headroom.

Battery rating and discharge behavior

Battery amp-hour ratings are usually quoted at a 20-hour rate. Higher discharge currents reduce usable capacity and increase voltage sag. A 100 Ah VRLA unit may deliver 60–80 Ah at a 1C discharge. If the calculated DC current exceeds 0.2C per string, increase parallel strings or select a larger Ah model. Lithium packs hold voltage better, but require certified battery management and matching charge profiles.

Derating, aging, and temperature

Plan for end-of-life capacity and the site environment. Many designs reserve 20–30% for aging across three to five years. Temperature effects are practical: at 0°C, lead-acid capacity can fall near 80% of rated, and at -10°C it can approach 70%. Heat also shortens life. Use a temperature factor when rooms are unconditioned. Depth of discharge matters: limiting DoD to 0.8 improves cycle life but increases required capacity.

Series-parallel configuration planning

Series batteries set the DC bus voltage; parallel strings set capacity. For a 48 V bus with 12 V units, series count is four and the actual bus is 48 V. Required amp-hours at the bus are Ah = Wh ÷ V. Example: 900 Wh ÷ 48 V is 18.75 Ah before derating. If the required capacity is 160 Ah, 100 Ah units need two parallel strings. Fuse each string, balance cable lengths, and verify connector ratings for the expected surge current.

Validation, documentation, and exports

After calculating, validate against manufacturer discharge tables and a runtime test. Record assumptions for auditability: efficiency, ripple factor, DoD, margins, and battery age. Log temperature and installation date. Keep a wiring sketch showing series count, parallel strings, and protective devices. Use the CSV for procurement comparisons and the PDF for maintenance manuals, inspections, and handover packages.

FAQs

What load value should I enter?

Enter the typical steady running watts you want to support. If you only know amperes, convert using real power, not VA. When unsure, measure with a power meter during normal operation.

Why does surge power matter?

Surge covers motor start, compressor inrush, and short transients. It affects surge current, inverter stress, and UPS headroom. Ignoring surge can cause unexpected shutdowns even when average load seems safe.

How should I choose depth of discharge?

For lead-acid, 0.5–0.8 DoD is common. Lower DoD extends life but increases battery count. For lithium, higher usable DoD is possible, but follow the manufacturer’s guidance and warranty limits.

What if my DC bus and battery voltage do not match?

The calculator sets series count using the ceiling of bus voltage divided by unit voltage. That creates a slightly higher actual bus voltage. Confirm the UPS accepts the resulting string voltage range.

Does the temperature factor replace environmental design?

No. Derating helps sizing, but ventilation and temperature control protect battery life and safety. Aim for stable room conditions and follow spacing and airflow recommendations from the UPS and battery suppliers.

When should I add more parallel strings?

Add strings when required amp-hours exceed a single battery’s rating, or when current per string is too high. More strings reduce discharge rate, improve voltage stability, and often increase real-world runtime consistency.

Related Calculators

Battery Capacity CalculatorBattery Energy CalculatorBattery Power CalculatorBattery Current DrawBattery Efficiency CalculatorBattery Degradation CalculatorBattery Health CalculatorBattery Thermal CalculatorBattery Internal ResistanceBattery Load Calculator

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.