Cooling Coil Condensate Calculator

Predict cooling coil water removal from psychrometric inputs. Compare drain rates and stored exports quickly. Plan piping with clear hourly, daily, and monthly estimates.

Calculator

Example Data Table

Airflow Entering Air Leaving Air Pressure Expected Result
1200 CFM 27 °C, 60% RH 13 °C, 95% RH 101.325 kPa About 5.8 L/hr
2500 CFM 30 °C, 65% RH 12 °C, 95% RH 101.325 kPa Higher condensate rate
800 CFM 24 °C, 50% RH 14 °C, 90% RH 95 kPa Lower condensate rate

Formula Used

The calculator estimates condensate from humidity ratio reduction across the coil.

W = 0.62198 × Pv / (P - Pv)

Pv = RH × Pws / 100

v = 0.287042 × T × (1 + 1.607858W) / P

ṁda = airflow / v

Condensate = ṁda × (Wentering - Wleaving) × drain efficiency

Optional latent load uses this relation:

Condensate kg/s = latent kW / 2450

The final design rate adds the selected safety factor.

How to Use This Calculator

Enter the cooling coil airflow first. Select the correct airflow unit.

Enter the entering dry bulb temperature and relative humidity.

Enter the leaving dry bulb temperature and relative humidity.

Use local barometric pressure when altitude is important.

Add runtime to estimate total collected condensate.

Set drain efficiency for pan loss or carryover allowance.

Add a safety factor for drain sizing and field variation.

Press Calculate. The result appears above the form.

Use CSV or PDF buttons to save the report.

Cooling Coil Condensate Calculation Guide

Why Condensate Forms

A cooling coil removes sensible heat from air. It also removes moisture when the coil surface is cold. Condensate appears when moist air is cooled below dew point. The water vapor changes into liquid water. This water must drain safely from the equipment.

What the Calculator Measures

This tool compares entering and leaving air conditions. It uses dry bulb temperature, relative humidity, and pressure. These values define the humidity ratio of the air. The humidity ratio means water vapor per dry air mass. The difference across the coil gives removed moisture.

Airflow and Pressure Matter

Airflow controls how much dry air crosses the coil. More airflow can carry more moisture. Pressure also affects humidity calculations. High altitude lowers air pressure. That changes specific volume and dry air flow. Use local pressure for better results.

Drain Sizing Use

The hourly condensate rate helps size pans and drains. The daily value helps estimate disposal volume. The monthly value helps compare seasonal water production. A safety factor is useful in humid climates. It also helps when coil data is uncertain.

Advanced Options

Drain efficiency adjusts the collected water amount. Coil bypass factor accounts for air not fully treated. Optional latent load gives a second calculation path. The calculator uses the larger moisture estimate. This supports design checks and service review.

Practical Notes

Results depend on accurate field readings. Measure temperatures after stable operation begins. Place sensors away from direct water spray. Use calibrated humidity instruments when possible. Check blocked drains, dirty filters, and low airflow. These problems can change the real condensate rate. The result is an engineering estimate. Final system design should follow local codes.

FAQs

What is cooling coil condensate?

It is liquid water formed when moist air passes over a cold coil. The coil cools air below dew point, so water vapor condenses on the surface.

Which input affects condensate most?

Entering humidity is very important. Airflow and leaving coil temperature also matter. High airflow with humid entering air usually creates more condensate.

Why do I need barometric pressure?

Pressure changes the humidity ratio and dry air volume. Sea level pressure works for many estimates, but local pressure improves accuracy at higher elevations.

What does coil bypass factor mean?

It estimates the portion of air that leaves without full contact with the cold coil surface. A higher bypass factor reduces predicted moisture removal.

Can this calculator size a drain line?

It helps estimate design flow. Use the design drain rate with plumbing rules, slope, trap needs, and local code before selecting a final drain size.

Why is my result zero?

The leaving air may not be drier than entering air. Check humidity values, temperature units, pressure, and sensor readings. The coil may be above dew point.

What is latent load?

Latent load is the cooling energy used to remove moisture. If known, it can estimate condensate from energy instead of psychrometric air conditions.

Are gallons and liters exact?

They are based on calculated mass and selected water density. Normal condensate is close to one kilogram per liter, so results are usually practical estimates.

Related Calculators

Paver Sand Bedding Calculator (depth-based)Paver Edge Restraint Length & Cost CalculatorPaver Sealer Quantity & Cost CalculatorExcavation Hauling Loads Calculator (truck loads)Soil Disposal Fee CalculatorSite Leveling Cost CalculatorCompaction Passes Time & Cost CalculatorPlate Compactor Rental Cost CalculatorGravel Volume Calculator (yards/tons)Gravel Weight Calculator (by material type)

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.