ERV Efficiency Mechanical Ventilation Calculator

Measure recovery with temperature and humidity readings fast safely. Check sensible, latent, and total efficiency. Estimate ventilation savings before balancing your mechanical system today.

Calculator Inputs

Formula Used

Sensible efficiency = |Outdoor dry bulb − Supply dry bulb| ÷ |Outdoor dry bulb − Return dry bulb| × 100.

Latent efficiency = |Outdoor humidity ratio − Supply humidity ratio| ÷ |Outdoor humidity ratio − Return humidity ratio| × 100.

Total efficiency = |Outdoor enthalpy − Supply enthalpy| ÷ |Outdoor enthalpy − Return enthalpy| × 100.

Humidity ratio uses saturation vapor pressure, relative humidity, and barometric pressure.

Recovered total energy = 4.5 × effective CFM × |outdoor enthalpy − supply enthalpy|.

Estimated fan watts = CFM × pressure drop × 746 ÷ (6356 × fan efficiency).

Net recovered energy = recovered total energy − fan watts × 3.412142.

How to Use This Calculator

  1. Enter outdoor air temperature and relative humidity before the ERV core.
  2. Enter return indoor air readings entering the exhaust side.
  3. Enter supply air readings leaving the ERV core.
  4. Add supply and exhaust airflow values from a balometer or test report.
  5. Add pressure drop and fan data for net recovery estimates.
  6. Use bypass and derate fields when leakage, frost, or dirt is known.
  7. Press Calculate to show results above the form.
  8. Use CSV or PDF downloads for records and reports.

Example Data Table

Case Outdoor Return Supply After ERV Airflow Expected Result
Humid cooling 95°F, 55% RH 75°F, 50% RH 82°F, 53% RH 1200 / 1150 CFM Strong sensible and total recovery
Winter heating 20°F, 60% RH 70°F, 35% RH 55°F, 38% RH 800 / 790 CFM High sensible recovery
Balanced mild day 68°F, 50% RH 72°F, 45% RH 70°F, 48% RH 600 / 600 CFM Low load but stable balance

Understanding ERV Efficiency

An energy recovery ventilator moves stale indoor air outside. It also brings fresh outdoor air inside. The core transfers heat and moisture between both airstreams. This process reduces the load on heating and cooling equipment. Efficiency shows how much outdoor air was preconditioned before it reached the room.

Important Readings

A good calculation needs three sets of readings. Measure outdoor air before the core. Measure return air entering the exhaust side. Measure supply air leaving the core. Temperature gives sensible recovery. Humidity ratio gives latent recovery. Enthalpy gives total recovery. These values describe different parts of comfort and energy use.

Efficiency Types

Sensible efficiency compares the temperature change caused by the core. It is useful for dry climates and heating checks. Latent efficiency compares moisture change. It matters in humid climates and dehumidification work. Total efficiency compares enthalpy. It includes both heat and moisture in one result.

Mechanical Ventilation Impact

Mechanical ventilation systems can look efficient but still waste power. Fans, dirty filters, pressure drop, and unbalanced airflow reduce net benefit. This calculator includes airflow, pressure, fan power, bypass, and derate inputs. These options help compare measured recovery with operating savings.

Airflow Balance

Balanced airflow is important. If supply airflow is much higher than exhaust airflow, the core cannot recover energy from all incoming air. If exhaust airflow is higher, the building may lose conditioned air. The calculator uses the lower airflow for recovered energy. It also reports the balance ratio for review.

Field Accuracy

Field readings need care. Use steady operation. Keep doors and bypass dampers in normal positions. Place sensors away from sun, coils, and wet surfaces. Let readings stabilize before recording values. Small humidity errors can change latent and total efficiency.

Use Results Carefully

The results should be used as engineering estimates. They are not a certified rating. Manufacturers test equipment under controlled standards. Field results can differ because airflow, installation, frost control, leakage, and maintenance vary. Still, a careful calculation is useful. It can show poor setup, fouled cores, or weak fan performance.

Better Decisions

Use the output to improve decisions. Compare sensible, latent, and total values together. Then check the net recovered energy. A high efficiency with high fan power may save less than expected. A moderate efficiency with low pressure drop can perform better during daily operation.

FAQs

What is ERV efficiency?

ERV efficiency shows how much heat or moisture transfer the core provides between outdoor air and exhaust air. It compares measured supply air against outdoor and return air conditions.

What is sensible efficiency?

Sensible efficiency measures temperature recovery only. It ignores moisture. It is helpful when checking heating performance, cooling performance, or dry climate operation.

What is latent efficiency?

Latent efficiency measures moisture recovery. It uses humidity ratio, not relative humidity alone. It matters most in humid climates and dehumidification checks.

What is total efficiency?

Total efficiency uses enthalpy. It includes both temperature and moisture energy. It is often the best single value for cooling season ventilation savings.

Why can efficiency exceed 100 percent?

Values above 100 percent usually mean unstable readings, sensor error, leakage, wrong sensor location, or active heating and cooling near the measurement point.

Why does airflow balance matter?

Unbalanced airflow limits recovery. The smaller airstream controls useful exchange. Poor balance can also affect building pressure and comfort.

Does fan power affect ERV savings?

Yes. Fan power reduces net savings. A core with good recovery can still perform poorly if pressure drop and fan watts are high.

Is this a certified ERV rating?

No. This is a field estimate for mechanical ventilation review. Certified ratings require controlled testing, fixed airflow, and standard test conditions.


Related Calculators

Paver Sand Bedding Calculator (depth-based)Paver Edge Restraint Length & Cost CalculatorPaver Sealer Quantity & Cost CalculatorExcavation Hauling Loads Calculator (truck loads)Soil Disposal Fee CalculatorSite Leveling Cost CalculatorCompaction Passes Time & Cost CalculatorPlate Compactor Rental Cost CalculatorGravel Volume Calculator (yards/tons)Gravel Weight Calculator (by material type)