NPSH Available Calculator

Compute NPSH available for suction conditions and fluids. Include altitude, vapor pressure, and losses easily. Get clear margins before selecting pumps and speeds properly.

Calculator Inputs

Use water near 20 C about 998 kg/m^3.
Altitude uses a standard atmosphere estimate.
Sea level is about 101.325 kPa.
Higher altitude reduces atmospheric head.
Negative values represent vacuum at the surface.
If pump is above surface, enter a negative value.
Include pipe, fittings, strainers, and valves.
For non-water fluids, enter vapor pressure directly.
Higher vapor pressure reduces NPSH available.
Used to estimate water vapor pressure only.
Velocity head is based on suction velocity.
If unsure, switch to flow and diameter mode.
Used to compute suction velocity.
Use the actual inside diameter, not nominal.
Reset

Formula Used

Net Positive Suction Head Available (NPSHa) expresses suction energy above the liquid vapor pressure at the pump inlet. A common head-form balance is:

NPSHa = Hatm + Hsurf + Hz - Hvap - Hf - Hv

How to Use This Calculator

  1. Enter the fluid density with the correct unit.
  2. Set atmospheric pressure directly, or estimate from altitude.
  3. Enter surface gauge pressure. Use zero for open tanks.
  4. Enter the static elevation difference. Positive helps suction.
  5. Enter suction friction losses based on your piping layout.
  6. Provide vapor pressure, or estimate it for water by temperature.
  7. Enter velocity head, or compute it from flow and diameter.
  8. Press calculate and compare with the pump requirement.

Practical tip: aim for extra margin above the pump requirement, especially for warm liquids or high suction losses.

Example Data Table

Case rho (kg/m^3) Patm (kPa) Psurf gauge (kPa) Hz (m) Hf (m) Pvap (kPa) Hv (m) NPSHa (m)
Water, mild suction 998 101.325 0 2.0 1.0 2.34 0.20 about 10.91
Warm water, higher vapor 992 101.325 0 1.0 1.8 7.38 0.30 about 8.49
Closed tank, slight pressure 998 101.325 20 0.5 1.2 2.34 0.15 about 12.18

Values are illustrative. Use measured data for design decisions.

Professional Guide

1) Why NPSH Available Matters

Net Positive Suction Head Available (NPSHa) is the absolute suction head above the liquid’s vapor pressure at the pump inlet. If NPSHa falls below the pump’s NPSH required (NPSHr), vapor bubbles can form and collapse, causing cavitation, noise, vibration, efficiency loss, and long-term impeller damage.

2) Key Inputs and Typical Ranges

This calculator combines atmospheric head, tank pressure, elevation, vapor pressure, friction losses, and velocity head. For water near 20 °C, density is about 998 kg/m³ and vapor pressure is roughly 2.34 kPa. Suction friction losses commonly range from 0.5–3 m depending on pipe length, fittings, and valves.

3) Atmospheric Pressure and Altitude Effects

Atmospheric head is often the largest positive term for open tanks. At sea level, 101.325 kPa corresponds to about 10.33 m of water. At higher altitudes the available atmospheric head decreases, reducing NPSHa. Use the altitude mode when site elevation is known and barometric data is unavailable.

4) Vapor Pressure and Temperature Influence

Vapor pressure rises rapidly with temperature, subtracting more head from NPSHa. Warm liquids are therefore more cavitation-prone. For water, vapor pressure is about 2.34 kPa at 20 °C and increases substantially as temperature approaches boiling. For hydrocarbons or solvents, always use manufacturer vapor pressure data.

5) Suction Losses and Piping Design

Suction-side losses are critical because they directly reduce NPSHa. Keep suction piping short, minimize elbows and restrictions, avoid undersized strainers, and limit sudden expansions. For long runs, increasing pipe diameter can cut friction losses significantly and improve suction stability.

6) Velocity Head and Flow Conditions

Velocity head accounts for kinetic energy at the suction nozzle and increases with suction velocity (V²/2g). High velocity is common with small pipes and high flow rates, raising losses and reducing NPSHa. Use the compute option to estimate velocity from flow rate and actual inner diameter.

7) Interpreting Results and Margin

Compare calculated NPSHa with pump NPSHr at the exact operating point (flow, speed, impeller trim, and liquid temperature). Many engineers target a margin above NPSHr to account for uncertainty, fouling, and transient conditions. If margin is tight, reduce losses, lower pump elevation, or pressurize the suction source.

8) Field Data Quality Tips

Use consistent reference elevations, measure pressure at the liquid surface or tank vapor space, and confirm whether readings are gauge or absolute. Verify fluid temperature at the suction source and check for flashing at control valves. Small measurement errors can shift NPSHa by meters in low-margin systems.

FAQs

1) What is the difference between NPSHa and NPSHr?

NPSHa is what your system provides at the pump inlet. NPSHr is what the pump needs at a given flow to avoid excessive cavitation. Always compare them at the same operating point.

2) Should I include velocity head in NPSHa?

Many pump standards include velocity head at the pump suction reference. If you do not know your practice, include it for conservatism, especially when suction velocities are high.

3) Why does warm water reduce NPSHa?

Warm water has higher vapor pressure. Higher vapor pressure subtracts more head in the NPSHa equation, making it easier for the liquid to flash and cavitate at the inlet.

4) Can I use this for closed tanks?

Yes. Enter the tank surface gauge pressure. Positive pressure increases NPSHa, while vacuum decreases it. Make sure your pressure value matches the unit and is truly gauge.

5) How do I estimate suction friction losses?

Use pipe friction methods and include fittings and valves as minor losses. If you have a measured suction pressure at the pump, you can back-calculate losses by comparing with the source conditions.

6) What if NPSHa is negative?

A negative result indicates vapor pressure plus losses exceed the available suction head. Recheck units, gauge versus absolute values, and elevation sign. In real systems, the pump will likely cavitate severely.

7) How much margin above NPSHr is recommended?

It depends on service severity and uncertainty. A larger margin is often used for hot liquids, variable operation, or dirty suction strainers. Follow your company standard and pump vendor guidance.