Southwire Wire Size Calculator

Size copper or aluminum conductors accurately. Review voltage drop, ampacity, conduit, and load factors quickly. Choose a safer wire size before final field verification.

Advanced Wire Size Calculator

A
V
°C
%
Ω/1000 ft
%

Example Data Table

Example Voltage Load Distance Material Phase Max Drop Typical Result
Small feeder 240 V 40 A 100 ft Copper Single phase 3% Often near 6 AWG
Motor branch 480 V 75 A 180 ft Copper Three phase 3% Often near 3 AWG
Long lighting run 120 V 18 A 220 ft Copper Single phase 3% Often upsized for drop

Formula Used

Design current: I design = load current × continuous factor × safety factor

DC voltage drop: VD = 2 × K × I × D ÷ CMA

Single phase AC voltage drop: VD = 2 × D × I × (R × PF + X × sinθ)

Three phase AC voltage drop: VD = √3 × D × I × (R × PF + X × sinθ)

Drop percent: VD% = VD ÷ system voltage × 100

Adjusted ampacity: base ampacity × ambient factor × conductor count factor

K is 12.9 for copper and 21.2 for aluminum. CMA means circular mil area. These equations estimate conductor behavior. Final selections must match the governing code and equipment limits.

How to Use This Calculator

  1. Enter the expected load current in amperes.
  2. Add the system voltage and circuit type.
  3. Enter the one-way conductor distance.
  4. Select copper or aluminum conductor material.
  5. Choose the insulation temperature rating.
  6. Enter ambient temperature and conductor count.
  7. Set the allowed voltage drop percentage.
  8. Press the calculate button.
  9. Review the recommended size and comparison table.
  10. Download the CSV or PDF report if needed.

Wire Sizing Article

Why Wire Size Matters

Wire size affects safety, voltage quality, heat, and equipment life. A small conductor can run hot. It can also waste energy. A long run can lose voltage before power reaches the load. This calculator checks both concerns. It compares ampacity and voltage drop together.

Ampacity And Heat

Ampacity is the current a conductor can carry. It depends on material, insulation rating, air temperature, and installation conditions. Copper usually carries more current than aluminum at the same size. Higher temperature insulation may allow a higher table value. Yet terminals may limit the final rating.

Voltage Drop

Voltage drop rises with current and distance. It falls when the conductor area increases. Low voltage drop helps motors start better. It also helps lights, heaters, chargers, and controls work correctly. Many designers target three percent for branch circuits. Feeders may need a different limit.

Advanced Inputs

This tool includes phase type, power factor, reactance, parallel runs, ambient correction, and conductor count adjustment. These inputs make the estimate more useful. A three phase circuit has a different drop equation. A direct current circuit uses a simpler loop calculation.

Practical Design Use

Start with the real load current. Mark continuous loads when they run for long periods. Add a safety margin when the project needs reserve capacity. Then compare the first passing conductor with larger choices. Bigger wire can reduce losses. It can also improve future flexibility.

Final Verification

This calculator is a planning aid. It does not replace local electrical rules. Conduit fill, terminal ratings, insulation type, temperature limits, and equipment instructions can change the final answer. Use the result as a strong estimate. Confirm the design before installation.

FAQs

1. What does this wire size calculator estimate?

It estimates the smallest listed conductor that meets selected ampacity and voltage drop limits. It also shows comparison rows for other conductor sizes.

2. Is copper always better than aluminum?

Copper has lower resistance and higher ampacity by size. Aluminum is lighter and often cheaper. The best choice depends on cost, terminals, distance, and installation rules.

3. Why does distance affect wire size?

Longer conductors have more resistance. More resistance causes more voltage drop. Larger conductors reduce that drop and improve delivered voltage.

4. What voltage drop limit should I use?

Three percent is a common design target for many branch circuits. Some feeders, motors, and sensitive equipment may need stricter checks.

5. What is a continuous load?

A continuous load runs for a long period. Selecting yes applies a 125 percent design factor. This gives a more conservative current value.

6. Why include ambient temperature?

High ambient temperature reduces a conductor’s cooling ability. The calculator applies a correction factor to reduce adjusted ampacity.

7. What do parallel runs mean?

Parallel runs split current across multiple conductors. This can help large loads. Parallel conductors must follow applicable installation rules.

8. Can this replace an electrician?

No. It is an estimating tool. Final conductor selection should be checked against local code, equipment labels, and professional judgment.

Related Calculators

Paver Sand Bedding Calculator (depth-based)Paver Edge Restraint Length & Cost CalculatorPaver Sealer Quantity & Cost CalculatorExcavation Hauling Loads Calculator (truck loads)Soil Disposal Fee CalculatorSite Leveling Cost CalculatorCompaction Passes Time & Cost CalculatorPlate Compactor Rental Cost CalculatorGravel Volume Calculator (yards/tons)Gravel Weight Calculator (by material type)

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.