Construction equipment sizing

AHU Electrical Load Calculator

Plan AHU electrical capacity with clear equipment-level calculations. Check demand, current, energy, and protective device requirements. Make informed design decisions before equipment procurement begins.

Enter AHU equipment data

Use nameplate values where possible. Fan ratings are treated as mechanical motor output. Other listed loads are treated as electrical input.

Select the AHU feeder configuration.
V
Use line voltage for three-phase systems.
Use a combined estimated value for the AHU.
%
Convert fan shaft output to electrical input.
%
Enter zero when no fan drive applies.
%
Use 100% when all loads run together.
kW
Mechanical shaft output from the motor rating.
kW
Mechanical shaft output. Enter zero when unused.
kW
Electrical input. Use dedicated equipment data.
kW
Use the installed heater bank rating.
kW
Enter electric steam or electrode load.
W
Include actuators, controls, lamps, and small loads.
%
Reserve capacity for prudent design flexibility.
%
Set by the governing electrical design basis.
h
Used only for the monthly energy estimate.
days
Used only for the monthly energy estimate.
Reset

Example Data Table

This example uses a 400 V three-phase AHU with a supply fan, return fan, electric heater, and control load.

Input Example value Purpose
Supply fan motor output7.50 kWPrimary air movement
Return fan motor output3.00 kWReturn air movement
Electric heater12.00 kWAir heating duty
Fan motor efficiency92%Converts output to input power
VFD loss allowance3%Allows for drive losses
Future capacity allowance20%Supports later expansion

Formula Used

The calculator uses simplified electrical planning formulas. It separates fan motor conversion from directly stated electrical loads.

Fan electrical input
Fan input kW = (Fan motor output kW ÷ Motor efficiency) × (1 + VFD loss)
Connected and design load
Connected kW = Supply fan + Return fan + Compressor + Heater + Humidifier + Controls
Design kW = Connected kW × Demand factor × (1 + Spare capacity)
Apparent power and current
kVA = Design kW ÷ Power factor
Three-phase A = Design kW × 1000 ÷ (√3 × Voltage × Power factor)
Single-phase A = Design kW × 1000 ÷ (Voltage × Power factor)
Preliminary circuit ampacity and energy
Minimum ampacity = Line current × Continuous-load factor
Monthly kWh = Diversity-adjusted operating kW × Daily hours × Monthly days

How to Use This Calculator

  1. Select the phase arrangement and enter the actual feeder voltage.
  2. Enter fan motor shaft ratings and their expected efficiency.
  3. Add direct electrical loads for heaters, humidifiers, compressors, and controls.
  4. Set demand, spare capacity, and continuous-load values from the project basis.
  5. Enter operating hours to estimate monthly energy consumption.
  6. Review the results above the form, then export or print them.

AHU Electrical Load Planning

An air handling unit combines several electrical loads. Fan motors usually dominate the base load. Electric heaters can quickly become the largest connected load. Humidifiers, compressors, controls, drain pumps, and accessories also matter. A useful calculation lists every item before selecting a feeder.

Start with the equipment schedule. Use actual nameplate values when they are available. A fan motor rating may show shaft output instead of electrical input. The calculator converts that rating with motor efficiency. It also adds a variable frequency drive allowance. This gives a better planning value for supply and return fans.

Electric heaters require close attention. Their rating is normally direct electrical input. A heater bank can raise current sharply during cold-weather operation. Humidifiers can behave similarly. Do not assume these loads operate at the same time unless the control sequence confirms it. Use a documented demand factor when diversity is valid.

Power factor affects feeder current. The same real power draws more current when power factor is lower. Three-phase current uses line voltage and the square-root-of-three relationship. Single-phase current uses voltage directly. Use the supply voltage that reaches the equipment, not a nominal value copied from another project.

The calculated minimum circuit ampacity includes your continuous-load factor. This is not the final conductor selection. Conductor size also depends on insulation rating, ambient temperature, installation method, grouping, voltage drop, and local rules. Breaker selection must consider motor starting, equipment protection limits, and manufacturer instructions.

Energy results help with budget planning. They use diversity-adjusted operating power, daily hours, and monthly operating days. Actual energy will vary with airflow, static pressure, weather, load control, and fan speed. A VFD can reduce fan energy substantially at part load. It does not eliminate the need for a proper full-load electrical check.

Keep the calculation with the design record. Update it after approved equipment submittals arrive. Compare the final nameplate MCA and MOCP values with the preliminary feeder. Review coordination with upstream protection. Confirm isolation, service access, earthing, control power, and emergency operating requirements before construction begins.

Good records also simplify commissioning. Mark each circuit source, disconnect, voltage, phase, load, and protection rating. Coordinate AHU controls with the electrical sequence. A locked rotor or inrush condition can influence protection. Review manufacturer starting guidance before finalizing distribution equipment for final feeder planning.

Important: This tool supports preliminary planning. A qualified electrical professional should complete final equipment and circuit design.

Frequently Asked Questions

1. What loads should an AHU calculation include?

Include supply and return fans, electric heaters, humidifiers, compressors, controls, pumps, dampers, lights, and manufacturer-listed accessories. Use dedicated feeder loads where equipment requires separate circuits.

2. Is fan motor kW always electrical input?

Not always. Some schedules show mechanical shaft output. Divide output by motor efficiency to estimate electrical input. Use the nameplate input or full-load current when it is available.

3. Why include a VFD loss allowance?

A variable frequency drive has conversion and control losses. Adding a modest allowance improves preliminary input-power estimates. Final design should use the selected drive manufacturer data.

4. What demand factor should I use?

Use 100% when listed loads can operate together. Reduce it only when a documented operating sequence prevents simultaneous operation. Do not use diversity merely to make a feeder smaller.

5. Does the calculator select the final breaker?

No. It shows a preliminary next standard size from calculated circuit ampacity. Final overcurrent protection must follow equipment instructions, motor requirements, coordination, and local electrical rules.

6. Why is power factor needed?

Power factor converts real power to apparent power and affects current. Lower power factor means higher current for the same kW. Use equipment data or a reasonable project estimate.

7. Can I use this for a packaged rooftop unit?

Yes, for preliminary planning. Enter electrical input values for compressor and heater sections. Verify the packaged unit nameplate MCA and MOCP before choosing conductors or protection.

8. What is the purpose of spare capacity?

Spare capacity reserves electrical headroom for future changes, options, or small upgrades. It is a project decision. It does not replace verification of actual installed equipment.

9. Does monthly energy equal utility billing energy?

No. It is an estimate based on entered hours and diversity. Billing energy changes with weather, fan control, occupancy, static pressure, heating demand, and maintenance condition.

10. Should electric heat use a motor efficiency value?

No. Electric resistance heater ratings are normally electrical input. Enter the heater kW directly. Do not divide heater load by fan motor efficiency.

11. What should be checked after the calculation?

Check nameplates, MCA, MOCP, short-circuit rating, voltage drop, conductor derating, disconnect rating, upstream coordination, isolation requirements, and the final approved control sequence.

Related Calculators

Paver Sand Bedding Calculator (depth-based)Paver Edge Restraint Length & Cost CalculatorPaver Sealer Quantity & Cost CalculatorExcavation Hauling Loads Calculator (truck loads)Soil Disposal Fee CalculatorSite Leveling Cost CalculatorCompaction Passes Time & Cost CalculatorPlate Compactor Rental Cost CalculatorGravel Volume Calculator (yards/tons)Gravel Weight Calculator (by material type)

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.