Dehumidification Load Calculator

Plan drying equipment with dependable dehumidification estimates today. Enter site airflows, targets, and moisture sources. Download results as tables for fast project decisions later.

Inputs
Choose airflow or room method, then calculate.
White theme · Responsive grid
Affects outdoor and target temperatures.
Used when selecting the airflow method.
Room method computes outdoor air rate from ACH.
Typical range: 5 to 45.
0–100%.
Sea level is about 101.325 kPa.
Used to compute target humidity ratio.
Common drying targets: 40–55%.
Capacity is reported per day using this value.
Includes ventilation + infiltration if known.
People add moisture through respiration.
Typical quiet work: 60–90 g/h-person.
Concrete curing, washing, or open water sources.
Common range: 5–20% for uncertainty.
Displays humidity ratios and intermediate terms.
Reset

Example data table

These scenarios show how ventilation and site moisture can drive capacity needs.

Scenario Outdoor Target Outdoor air rate Internal moisture Estimated daily removal
Small refurbishment bay 30°C, 65% 24°C, 50% 600 m³/h 0.20 kg/h ≈ 65 L/day
Concrete curing zone 33°C, 75% 24°C, 45% 900 m³/h 0.60 kg/h ≈ 135 L/day
Large enclosure 28°C, 70% 22°C, 50% 2000 m³/h 1.20 kg/h ≈ 290 L/day
Example numbers are illustrative; measure site conditions for best results.

Formula used

This calculator estimates the moisture removal required to maintain a target indoor humidity.

1) Humidity ratio
W = 0.62198 × Pv / (P − Pv)
Pv is water vapor partial pressure (kPa). P is barometric pressure (kPa).
2) Ventilation moisture load
w,vent = ṁda × max(0, Wout − Wtarget)
da is dry-air mass flow (kg dry air/h). Result is kg water/h.
3) Total moisture removal
w,total = (ṁw,vent + ṁw,int) × (1 + SF)
Internal moisture adds occupants and processes. SF is the safety factor.
4) Latent load
Q̇ = (ṁw,total/3600) × hfg
hfg is latent heat (kJ/kg). Output is in kW.
Tip: If outdoor air is drier than your target, ventilation load becomes zero.

How to use this calculator

  1. Enter outdoor temperature and relative humidity from site measurements.
  2. Set your target indoor temperature and relative humidity for drying.
  3. Choose a method: input outdoor air rate, or use volume and ACH.
  4. Add moisture sources: occupants and wet materials or processes.
  5. Apply a safety factor, then calculate to get capacity needs.
  6. Download the CSV or PDF for reporting and approvals.

Outdoor Air and Infiltration Drive Latent Load

Dehumidification demand rises when humid outdoor air enters an enclosure through doors, gaps, or pressure-driven leakage. The calculator converts outdoor temperature and relative humidity into a humidity ratio (W) and compares it to the target indoor W. The difference (ΔW) is multiplied by dry-air mass flow to estimate ventilation moisture. As a rule, doubling outdoor air from 600 to 1200 m³/h can nearly double required removal when RH exceeds 60%.

Choosing Targets for Drying and Material Protection

Targets should match drying goals and material limits. Many projects aim for 40–55% indoor RH with temperatures near 20–26°C to balance comfort and evaporation. Lower RH increases removal and helps control corrosion and mold risk, but it may require more equipment. This tool reports kg/h and L/day so you can compare setpoints against dehumidifier ratings and project acceptance criteria, and improves worker visibility.

Internal Moisture Sources in Active Construction Sites

Internal sources can dominate when air exchange is controlled. A light-activity moisture rate is often 60–90 g/h per person, so ten workers can add roughly 0.6–0.9 kg/h. Wet concrete curing, wash-down, open sumps, and exposed soil can add several kg/h depending on area, temperature, and airflow over the surface. Enter known process moisture directly, then apply a safety factor for shifts and staging.

Interpreting Results: kg/h, L/day, kW, and Btu/h

Moisture removal in kg/h is the core sizing number; one kilogram of water is about one liter. Multiplying by operating hours yields L/day and US pints/day for nameplate comparisons. The latent load in kW and Btu/h is derived from moisture rate and latent heat, supporting generator sizing and coordination with temporary cooling or heat rejection. If runtime is limited, required daily capacity increases.

Field Tips for Improving Accuracy and Reducing Capacity

Improve accuracy with measurements. Use calibrated meters, log readings at least twice daily, and note weather changes. Confirm airflow using fan curves, damper positions, or simple smoke tests, and remember that negative pressure increases infiltration. Use the room method (Volume × ACH) for early planning, then switch to measured airflow after barriers are installed. Sealing leaks and isolating wet zones often reduces capacity more than changing setpoints, and stabilizes drying schedules.

FAQs

What input should I use if I only know exhaust fan CFM?

Select the airflow method, set airflow units to CFM, and enter the delivered fan CFM. Use the actual operating point if filters, ducting, or static pressure reduce flow.

Why does ventilation moisture load sometimes show zero?

If outdoor air has a lower humidity ratio than the indoor target, bringing it in does not add moisture. The calculator clamps ΔW to zero so the ventilation term cannot become negative.

What safety factor is reasonable for construction drying?

A common starting point is 5–20%. Use the higher end when openings change often, wet trades overlap, or measurements are limited. Reduce it once airflow and moisture sources are verified.

How do I estimate process moisture from wet concrete?

If you cannot measure evaporation, enter a conservative provisional value based on wet area and conditions. Refine it after observing indoor RH trends and comparing them to collected condensate volumes.

Should I size equipment based on liters per day or kW?

Use liters per day or pints per day to match dehumidifier capacity ratings. Use kW and Btu/h for power planning, heat rejection, and coordination with HVAC or temporary cooling.

Does changing temperature units affect the calculation?

No. The calculator converts °F to °C internally before computing humidity ratio and latent load. Results are consistent; only the input and display units change.

Related Calculators

Mold Moisture Source CalculatorIndoor Humidity Risk CalculatorDew Point Mold CalculatorSurface Condensation Risk CalculatorWall Cavity Moisture CalculatorBasement Dampness Index CalculatorVentilation Rate Mold CalculatorAir Exchange Need CalculatorBathroom Exhaust Sizing CalculatorKitchen Ventilation Need Calculator

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.