Duct Static Pressure Calculator

Quickly size duct runs and predict pressure drop. Account for fittings, filters, coils, and dampers. Export reports for submittals, estimates, and commissioning checks today.

Inputs Use the grid; it adapts by screen size.
Multiplies total pressure loss (≥ 1.0).
Use for extra runs or allowances.
Use for extra runs or allowances.
Typical indoor air is ~1.20 kg/m³.
Typical at 20°C is 1.81e−5 Pa·s.
Used to estimate friction factor.

Fittings (K-method)

Enter counts and adjust K if needed. Loss = K × (ρV²/2).
Tip: If velocity is high, fitting losses rise quickly.
90° elbow (radius)
Default K: 0.35
90° elbow (mitered)
Default K: 1.5
45° elbow
Default K: 0.2
Tee (through run)
Default K: 1
Tee (branch)
Default K: 1.8
Wye
Default K: 0.6
Duct entry
Default K: 0.5
Duct exit
Default K: 1
Sudden expansion
Default K: 0.8
Sudden contraction
Default K: 0.4

Equipment losses

Enter typical component drops. Use in.wg for Imperial, or Pa for SI.
What counts as equipment?
Include anything not captured by straight duct or fittings: filters, coils, heat recovery, silencers, VAV boxes, or specialty devices.
Reset
Downloads include your latest calculated inputs and results.

Example data table

Scenario Flow Duct Length Fittings Equipment Typical total loss
Office supply run 1200 CFM 14 in round 80 ft 4× 90° radius elbows Filter 0.30, coil 0.25 in.wg ~1.0–1.8 in.wg (depends on fittings)
Short branch 450 CFM 10×6 in rect 35 ft 2× elbows, 1× branch tee Damper 0.08 in.wg ~0.4–0.9 in.wg
High velocity run 2000 CFM 12 in round 60 ft Many fittings Terminal 0.12 in.wg Often >2.0 in.wg

Formula used

1) Velocity

V = Q / A, where Q is flow rate and A is cross‑sectional area.

2) Velocity pressure

q = ρ V² / 2, where ρ is air density.

3) Straight duct loss (Darcy–Weisbach)

ΔP_straight = f (L / Dh) q. For rectangular ducts, Dh = 2ab/(a+b).

4) Fitting loss (K-method)

ΔP_fittings = (Σ K) q.

5) Total static loss

ΔP_total = (ΔP_straight + ΔP_fittings + ΔP_equipment) × SafetyFactor.

How to use this calculator

  1. Choose a unit system that matches your drawings and schedules.
  2. Enter flow rate, duct size, and total straight length.
  3. Select duct material roughness or enter a custom value.
  4. Add fitting counts and adjust K values if you have project data.
  5. Enter equipment drops from product submittals and shop drawings.
  6. Click Calculate and review straight, fittings, and equipment breakdown.
  7. Use CSV or PDF export for estimates, reviews, and commissioning.

Professional notes

1) Why static pressure drives fan selection

Supply and return fans must overcome total system resistance, which is the sum of duct friction, fitting turbulence, and component pressure drops. In many comfort systems, total external static pressure commonly falls between 0.5 and 2.5 in.wg, depending on duct velocity, filtration level, and accessories.

2) Velocity is the hidden cost multiplier

Pressure losses scale with velocity pressure q = ρV²/2. If velocity increases by 20%, velocity pressure rises by 44%. That increase affects both straight runs and fittings, so “small” layout changes can materially shift total pressure and fan brake horsepower.

3) Straight duct loss and surface roughness

The calculator uses Darcy–Weisbach for straight duct loss and estimates friction factor from Reynolds number and relative roughness. Smooth materials reduce friction, while flexible or ductboard sections typically increase resistance. When mixing materials, model the highest-loss segments explicitly.

4) Fittings and transitions often dominate

Elbows, tees, entries, exits, and abrupt transitions convert flow energy into turbulence. Their loss is captured with the K‑method: ΔP = (ΣK)q. For high-velocity mains, a handful of fittings can add as much loss as tens of meters of straight duct, especially on branch takeoffs.

5) Commissioning and reporting

Use measured device drops from submittals (filters, coils, silencers, dampers) and apply a modest safety factor when routing is uncertain. Export the results to document assumptions, compare alternates, and support TAB targets. If measured field pressure deviates, adjust K values and lengths to calibrate.

FAQs

1) What is duct static pressure?

It is the resistance a fan must overcome to move air through ducts, fittings, and devices. It is commonly reported in Pa or inches of water column.

2) Why do fittings matter so much?

Fitting losses rise with velocity pressure, so higher air speed increases turbulence losses quickly. Elbows, tees, and abrupt transitions can dominate total pressure in compact layouts.

3) When should I apply a safety factor?

Use it when routing is not finalized, when future accessories may be added, or when filter loading is expected to increase. Keep it modest and document the basis.

4) Can I use this for return air ducts?

Yes. The same loss methods apply to supply and return. Enter the correct flow rate and include grilles, dampers, filters, and any terminal devices that add pressure drop.

5) What happens at very low airflow?

Flow can approach laminar conditions. The calculator uses a laminar friction relation when Reynolds number is below 2300, which changes how straight-duct loss scales with velocity.

6) Are K values always the same?

No. K depends on geometry, radius, angle, and fabrication quality. Use handbook or manufacturer values when available, then adjust K here to match project assumptions or field findings.

7) Does this replace full duct design?

It supports rapid loss estimates and documentation. Detailed design may still require equal‑friction or static‑regain methods and verified fitting data for each branch, terminal, and control device.

1) What is duct static pressure?

It is the pressure a fan must overcome to move air through ducts, fittings, and devices. It is typically reported as Pa or inches of water column.

2) Why do fittings matter so much?

Fittings create turbulence and separation. Their loss rises with velocity pressure, so high air speed can make elbows, tees, and transitions dominate total pressure.

3) When should I use a safety factor?

Use it when duct routing is uncertain, when accessories may be added, or when cleanliness will change over time. Keep it modest and document the basis.

4) Can I use this for return air systems?

Yes. The same loss methods apply to supply and return runs. Make sure you use the correct flow rate and include devices such as grilles, dampers, and filters.

5) What if my airflow is very low?

At low Reynolds numbers, flow may be laminar and friction behavior changes. The calculator switches to a laminar friction relation when Reynolds number is below 2300.

6) Are K values universal?

No. K depends on geometry, radius, angle, and fabrication. Use manufacturer or handbook values when available, then adjust here to match your project assumptions.

7) Does this replace a full duct design?

It helps estimate losses quickly, but detailed design may require full equal‑friction or static‑regain methods and verified fitting data for each branch and terminal.

Related Calculators

Paver Sand Bedding Calculator (depth-based)Paver Edge Restraint Length & Cost CalculatorPaver Sealer Quantity & Cost CalculatorExcavation Hauling Loads Calculator (truck loads)Soil Disposal Fee CalculatorSite Leveling Cost CalculatorCompaction Passes Time & Cost CalculatorPlate Compactor Rental Cost CalculatorGravel Volume Calculator (yards/tons)Gravel Weight Calculator (by material type)

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.