Quickly size duct runs and predict pressure drop. Account for fittings, filters, coils, and dampers. Export reports for submittals, estimates, and commissioning checks today.
| Scenario | Flow | Duct | Length | Fittings | Equipment | Typical total loss |
|---|---|---|---|---|---|---|
| Office supply run | 1200 CFM | 14 in round | 80 ft | 4× 90° radius elbows | Filter 0.30, coil 0.25 in.wg | ~1.0–1.8 in.wg (depends on fittings) |
| Short branch | 450 CFM | 10×6 in rect | 35 ft | 2× elbows, 1× branch tee | Damper 0.08 in.wg | ~0.4–0.9 in.wg |
| High velocity run | 2000 CFM | 12 in round | 60 ft | Many fittings | Terminal 0.12 in.wg | Often >2.0 in.wg |
1) Velocity
V = Q / A, where Q is flow rate and A is cross‑sectional area.
2) Velocity pressure
q = ρ V² / 2, where ρ is air density.
3) Straight duct loss (Darcy–Weisbach)
ΔP_straight = f (L / Dh) q. For rectangular ducts, Dh = 2ab/(a+b).
4) Fitting loss (K-method)
ΔP_fittings = (Σ K) q.
5) Total static loss
ΔP_total = (ΔP_straight + ΔP_fittings + ΔP_equipment) × SafetyFactor.
Supply and return fans must overcome total system resistance, which is the sum of duct friction, fitting turbulence, and component pressure drops. In many comfort systems, total external static pressure commonly falls between 0.5 and 2.5 in.wg, depending on duct velocity, filtration level, and accessories.
Pressure losses scale with velocity pressure q = ρV²/2. If velocity increases by 20%, velocity pressure rises by 44%. That increase affects both straight runs and fittings, so “small” layout changes can materially shift total pressure and fan brake horsepower.
The calculator uses Darcy–Weisbach for straight duct loss and estimates friction factor from Reynolds number and relative roughness. Smooth materials reduce friction, while flexible or ductboard sections typically increase resistance. When mixing materials, model the highest-loss segments explicitly.
Elbows, tees, entries, exits, and abrupt transitions convert flow energy into turbulence. Their loss is captured with the K‑method: ΔP = (ΣK)q. For high-velocity mains, a handful of fittings can add as much loss as tens of meters of straight duct, especially on branch takeoffs.
Use measured device drops from submittals (filters, coils, silencers, dampers) and apply a modest safety factor when routing is uncertain. Export the results to document assumptions, compare alternates, and support TAB targets. If measured field pressure deviates, adjust K values and lengths to calibrate.
It is the resistance a fan must overcome to move air through ducts, fittings, and devices. It is commonly reported in Pa or inches of water column.
Fitting losses rise with velocity pressure, so higher air speed increases turbulence losses quickly. Elbows, tees, and abrupt transitions can dominate total pressure in compact layouts.
Use it when routing is not finalized, when future accessories may be added, or when filter loading is expected to increase. Keep it modest and document the basis.
Yes. The same loss methods apply to supply and return. Enter the correct flow rate and include grilles, dampers, filters, and any terminal devices that add pressure drop.
Flow can approach laminar conditions. The calculator uses a laminar friction relation when Reynolds number is below 2300, which changes how straight-duct loss scales with velocity.
No. K depends on geometry, radius, angle, and fabrication quality. Use handbook or manufacturer values when available, then adjust K here to match project assumptions or field findings.
It supports rapid loss estimates and documentation. Detailed design may still require equal‑friction or static‑regain methods and verified fitting data for each branch, terminal, and control device.
It is the pressure a fan must overcome to move air through ducts, fittings, and devices. It is typically reported as Pa or inches of water column.
Fittings create turbulence and separation. Their loss rises with velocity pressure, so high air speed can make elbows, tees, and transitions dominate total pressure.
Use it when duct routing is uncertain, when accessories may be added, or when cleanliness will change over time. Keep it modest and document the basis.
Yes. The same loss methods apply to supply and return runs. Make sure you use the correct flow rate and include devices such as grilles, dampers, and filters.
At low Reynolds numbers, flow may be laminar and friction behavior changes. The calculator switches to a laminar friction relation when Reynolds number is below 2300.
No. K depends on geometry, radius, angle, and fabrication. Use manufacturer or handbook values when available, then adjust here to match your project assumptions.
It helps estimate losses quickly, but detailed design may require full equal‑friction or static‑regain methods and verified fitting data for each branch and terminal.
Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.