Pick dependable MV cable sizes for your site. Check current, derating, and voltage drop. Export results for reviews, procurement, client documentation, and approvals records.
Gather the maximum demand, duty cycle, and likely growth. For motors, use rated kW, realistic efficiency, and a measured or specified power factor. For feeders, kVA is often easier because it already includes reactive demand. This calculator converts kW or kVA into current using standard AC relationships. For example, 1500 kW at 11 kV, pf 0.90, and efficiency 0.95 is about 92 A before margin.
Medium-voltage distribution commonly falls around 6.6 kV, 11 kV, or 33 kV in many projects. Small voltage changes shift current significantly, so always confirm nominal voltage and the operational tolerance band. Select single-phase only for dedicated single-phase MV applications.
Cable ampacity depends on heat removal. Higher ambient temperature, grouping of loaded circuits, and enclosed routes reduce cooling. The tool combines temperature, grouping, and installation factors into one total derating multiplier and applies it to a typical base ampacity. Use site-specific thermal resistivity, duct spacing, and depth when finalizing designs. In high-resistivity soil or crowded duct banks, derating can dominate, so conservative inputs help avoid late redesign.
Long MV routes can experience noticeable drop even when ampacity is adequate. The calculator estimates drop using typical resistance and reactance per kilometer, plus your power factor. Document the installed route length, not just map distance. Tight limits (for example, 2–3%) often push the selection to larger conductors or parallel runs, especially for high-current feeders.
Record the input basis, derating selections, and the selected size for internal checks, client approvals, and procurement. Export the results as CSV for calculation packs, and use the PDF summary for quick sharing. Always confirm the final cable with manufacturer datasheets, termination limits, and the governing standard.
No. It is a screening result using typical catalog values and simplified derating. Final sizing should follow the applicable standard, manufacturer ampacity tables, installation details, and project review requirements.
Use kW when you know real power and have reasonable power factor and efficiency values. Use kVA for feeders or transformers where apparent power is specified and efficiency is not part of the current calculation.
Higher ambient temperature and grouped circuits make it harder for heat to escape. The conductor runs hotter for the same current, so allowable current must be reduced to keep insulation temperature within limits.
Parallel runs split the design current across identical cables installed in the same way. The calculator divides current per run and then checks ampacity and voltage drop for each run’s conductor size.
The tool uses an AC approximation with resistance and reactance per kilometer and your power factor. It estimates drop as a percentage of system voltage, which is useful for comparing sizes during early design.
On long routes, resistance and reactance cause voltage reduction even if the cable can carry the current thermally. Larger conductors, improved power factor, or additional parallel runs are typical solutions.
They are typical, illustrative values for comparison only. Different constructions, screens, conductor stranding, installation methods, and manufacturer data can change ampacity and impedance. Always validate with approved product data.
| Material | Size (mm2) | Base Ampacity (A) | R (ohm/km) | X (ohm/km) |
|---|---|---|---|---|
| Cu | 35 | 180 | 0.524 | 0.08 |
| Cu | 50 | 210 | 0.387 | 0.08 |
| Cu | 70 | 255 | 0.268 | 0.08 |
| Cu | 95 | 300 | 0.193 | 0.08 |
| Cu | 120 | 340 | 0.153 | 0.08 |
| Cu | 150 | 380 | 0.124 | 0.08 |
| Cu | 185 | 420 | 0.0991 | 0.08 |
| Cu | 240 | 480 | 0.0754 | 0.08 |
Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.